Oil Cooler 
The oil must be cooled when the compressor is running.
EX Compressors: This is accomplished through a small, plate-type heat exchanger. The heat 
exchanger uses liquid condenser refrigerant as the cooling liquid. A refrigerant thermostatic 
expansion valve (TXV) regulates refrigerant flow to control oil temperature entering the 
bearings. There is always a flow of refrigerant bypassing the TXV. The bulb for the expansion 
valve is strapped to the oil supply line leaving the heat exchanger and the valve is set to 
maintain 110 F (43 C).
Note: The expansion valve is not adjustable. Oil sump temperature may be at a lower tempera-
ture. 
FA Compressors: The oil cooler is a water cooled, tube-in-shell type heat exchanger. A plug 
valve is manually set to maintain proper temperatures. Set the valve to maintain 145 F (63 C) oil 
sump temperatures while the compressor is running.
Remote Start/Stop Controls
A remote device, such as a timeclock which uses a set of contacts, may be used to start and 
stop the machine. However, the device should not be programmed to start and stop the 
machine in excess of 2 or 3 times every 12 hours. If more than 8 starts in 12 hours occur, then 
an Excessive Starts alarm is displayed, preventing the machine from starting. The operator 
must reset the alarm at the LID in order to override the starts counter and start the machine. If