Oil Sump Temperature Control 
The oil sump temperature control is regulated by the PIC which uses the oil heater relay 
when the machine is shut down. 
As part of the pre-start checks executed by the controls, oil sump temperature is compared 
against evaporator refrigerant temperature. If the difference between these 2 temperatures is 
50 F (27.8 C) or less, the start-up will be delayed until the oil temperature is 50 F (27.8 C) or 
more. Once this temperature is confirmed, the start-up continues. 
The oil heater relay is energized whenever the chiller compressor is off and the oil sump 
temperature is less than 150 F (65.6 C) or the oil sump temperature is less than the cooler 
refrigerant temperature plus 70° F (39° C). The oil heater is turned off when the oil sump 
temperature is either 1) more than 160 F (71.1 C); or 2) the oil sump temperature is more than 
155 F (68.3 C) and more than the cooler refrigerant temperature plus 75° F (41.6° C). The oil 
heater is always off during start-up or when the compressor is running. 
When a power failure to the PSIO module has occurred for more than 3 hours (i.e., initial 
start-up), the compressor guide vane opening will be slowed down to prevent excessive oil 
foaming that may result from refrigerant migration into the oil sump during the power failure. 
The vane opening will be slowed to a value of 2° F (1.1° C) per minute with temperature ramp 
loading.