13
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Quick Setup Instructions
QUICK SETUP INSTRUCTIONS
These instructions assume the meter is set to factory defaults. If it has been 
previously configured, all optional values should be checked.
1.  Press the 
+
 or 
 button repeatedly until SETUP screen appears.
2.  Press   to the PASWD screen.
3.  Press   through the digits. Press 
+
 or 
 to select the password (the default 
is 00000). Exit the screen to the right.
4.  Press 
+
 or 
 to select the parameter to configure.
5.  The first Setup screen is S COM (set RS-485 communications). 
a.  Press   to the ADDR screen and through the address digits. Press 
+
 
or 
 to select the Modbus address.
b.  Press   to the BAUD screen. Press 
+
 or 
 to select the baud rate.
c.  Press   to the PAR screen. Press 
+
 or 
 to select the parity.
d.  Press   back to the S COM screen. 
6.  Press 
 to the S CT (Set Current Transducer) screen. 
a.  Press   to the CT V screen. Press 
+
 or 
 to select the voltage mode 
Current Transducer output voltage (default is 0.33).
b.  Press   to the CT SZ screen and through the digits. Press 
+
 or 
 to 
select the CT size in amps.
c.  Press   back to the S CT screen. 
7.  Press 
 to the S SYS (Set System) screen. 
a.  Press   to the SYSTM screen. Press 
+
 or 
 to select the System Type 
(see wiring diagrams).
b.  Press   back to the S SYS screen. 
8.  (Optional) Press 
 to the S PT (Set Potential Transformer) screen. If PTs 
are not used, then skip this step.
a.    to the RATIO screen and through the digits. Use the 
+
 or 
 buttons 
to select the Potential Transformer step down ratio.
b.    back to the S PT screen. 
9.  
 to the S  V (Set System Voltage) screen. 
a.    to the VLL (or VLN if system is 1L-1n) screen and through the digits. 
Use the 
+
 or 
 buttons to select the Line to Line System Voltage. 
b.    back to the S  V screen. 
10.  Use the   to exit the setup screen and then SETUP.
11.  Check that the wrench is not displayed on the LCD. 
a.  If the wrench is displayed, press 
+
 or 
 to find the ALERT screen.
b.  Press   through the screens to see which alert is on.
For full setup instructions, see the configuration instructions on the following 
pages.