Schneider Electric EM3555 Manual De Usuario

Descargar
Página de 46
14
© 2011 Schneider Electric All Rights Reserved.
EM3555
Solid-state Pulse Output
ZL0093-0A
11/2011
SOLID-STATE PULSE OUTPUT
The meter has one normally open (N.O.) KY Form A output and one normally 
closed (N.C.) solid-state output.* One is dedicated to import energy (Wh), and 
the other to Alarm. See the Setup section for configuration information.
Figure 6  Solid State Pulse Outputs
~
=
≤ 100 mA
~
=
≤ 100 mA
Alarm
Energy
Output
+         –         S
Power Source
3-30 VDC
6-30 VAC
Power Source
3-30 VDC
6-30 VAC
Over-Current Protective
Device** (not supplied)
The solid state pulse outputs are rated for 30 VAC/DC nom.
Maximum load current is 100 mA at 25°C. Derate 0.56 mA per °C above 25°C.
* While the relay used for the Phase Loss contact is Normally Closed (contacts 
are closed when the meter is not powered), closure indicates the presence of an 
alarm; either loss of phase, when the meter is powered, or loss of power when 
the meter is not. The contacts are open when the meter is powered and no 
phase loss alarm conditions are present.
** The over-current protective device must be rated for the short circuit current 
at the connection point.