Schneider Electric EM3555 Manual De Usuario

Descargar
Página de 46
1
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Safety Precautions
SAFETY PRECAUTIONS
  
DANGER
 
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•  Follow safe electrical work practices. See NFPA 70E in the USA or 
applicable local codes.
•  This equipment must only be installed and serviced by qualified 
electrical personnel.
•  Read, understand, and follow the instructions before installing this 
product.
•  Turn off all power supplying equipment before working on or inside 
the equipment.
•  Always use a properly rated voltage sensing device to confirm power is 
off.
•  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION.
•  Only install this product on insulated conductors.
•  Install device in an appropriate electrical and fire enclosure per local 
regulations.
•  ESD sensitive equipment. Ground yourself and discharge any static 
charge before handling this device.
•  Any covers that may be displaced during the installation must be 
reinstalled before powering the unit.
•  Do not install on the load side of a Variable Frequency Drive (VFD), aka 
Variable Speed Drive (VSD) or Adjustable Frequency Drive (AFD).
 
 Failure to follow these instructions will result in death or serious injury.
  
    
INSTALLATION OVERVIEW
NOTE:  Observe correct CT orientation.
The meter can be mounted in two ways:  on standard 35 mm DIN rail or 
screw-mounted to the interior surface of the enclosure.
A. DIN Rail Mounting
1.  Disconnect and lock out power. Use a properly rated voltage sensing device 
to confirm power is off.
2.  Attach mounting clips to the underside of the housing by sliding them into 
the slots from the inside. The stopping pegs must face the housing, and the 
outside edge of the clip must be flush with the outside edge of the housing.
3.  Snap the clips onto the DIN rail.
4.  To prevent horizontal shifting across the DIN rail, use two end stop clips. 
B. Screw Mounting
1.  Disconnect and lock out power. Use a properly rated voltage sensing device 
to confirm power is off.
2.  Attach the mounting clips to the underside of the housing by sliding them 
into the slots from the outside. The stopping pegs must face the housing, 
and the screw hole must be exposed on the outside of the housing.
3.  Use three #8 screws (not supplied) to mount the meter to the inside of the 
enclosure. 
NOTE:  For detailed instructions, please see the “Installation” section 
later in this guide.