Schneider Electric EM3555 Manual De Usuario

Descargar
Página de 46
3
© 2011 Schneider Electric All Rights Reserved.
ZL0093-0A
11/2011
EM3555
Specifications
Type
Description
Environmental Conditions
Operating  Temperature                                            -30° to 70°C (-22° to 158°F)
Storage Temperature
-40° to 85°C (-40° to 185°F)
Humidity Range
<95% RH (non-condensing)
Altitude of Operation
3 km max.
Metering Category
US and Canada
CAT III; for distribution systems up to 347 V 
L-N  
/600 VAC 
L-L
CE
CAT III; for distribution systems up to 300 V
 L-N 
/480 VAC 
L-L
Dielectric Withstand
Per UL 508, EN61010 
Conducted and Radiated 
Emissions
FCC part 15 Class B, EN55011/EN61000 Class B; 
(residential and light industrial)
Conducted and Radiated 
Immunity
EN61000 Class A (heavy industrial)
Safety
US and Canada (cULus)
UL508 (open type device)/CSA 22.2 No. 14-05
Europe (CE)
EN61010-1:2001
* External DC current limiting is required, see fuse recommendations.
For use in a Pollution Degree 2 or better environment only. A Pollution 
Degree 2 environment must control conductive pollution and the possibility of 
condensation or high humidity. Consideration must be given to the enclosure, 
the correct use of ventilation, thermal properties of the equipment and the 
relationship with the environment.
Always use this product in the manner specified or the protection provided by 
the product may be impaired.
Provide a disconnect device to disconnect the meter from the supply source. 
Place this device in close proximity to the equipment and within easy reach 
of the operator, and mark it as the disconnecting device. The disconnecting 
device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3 
and shall be suitable for the application. In the US and Canada, disconnecting 
fuse holders can be used. Provide overcurrent protection and disconecting 
device for supply conductors with approved current limiting devices suitable for 
protecting the wiring. If the equipment is used in a manner not specified by the 
manufacturer, the protection provided by the device may be impaired.
FCC PART 15 INFORMATION
NOTE:  This equipment has been tested by the manufacturer and found 
to comply with the limits for a class B digital device, pursuant to part 15 of 
the FCC Rules. These limits are designed to provide reasonable protection 
against harmful interference when the equipment is operated in a residential 
environment. This equipment generates, uses, and can radiate radio frequency 
energy and, if not installed and used in accordance with the instruction 
manual, may cause harmful interference to radio communications. Operation 
of this equipment in a residential area may cause harmful interference in 
which case the user will be required to correct the interference at his own 
expense. Modifications to this product without the express authorization of the 
manufacturer nullify this statement.
       
       
N998