Schneider Electric PM5100 Manual De Usuario

Descargar
Página de 96
PowerLogic™ PM5100 series user guide 
Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved
13
Chapter 3—Hardware Reference
This section supplements the meter’s installation sheet and provides additional 
information about the meter’s physical characteristics and capabilities.
Models, Features and Options
Table 3 –1: PM5100 Series - Models, Features and Options
Functions and Characteristics
Table 3 –2: Functions and Characteristics
Features and Options
PM5100 series
PM5100
PM5110
PM5111
Installation
Fast installation, panel mount with integrated 
display
 Accuracy 
Cl 0.5S
Cl 0.5S
Cl 0.5S
 Display 
Backlit LCD, multilingual, bar graphs, 6 lines, 4 
concurrent values
Power and energy metering
3-phase voltage, current, power, demand, 
energy, frequency, power factor
Power quality analysis
THD, thd, TDD
Harmonics, individual (odd) up to
15th
15th
15th
I/Os
Digital output
1DO
1DO
1DO
Alarms and control
Alarms
33
33
33
Set point response time, seconds
1
1
1
Communications
Serial ports with modbus protocol
0
1
1
MID ready compliance,
EN50470-1/3, Annex B and Annex D
Class C
General
PM5100 Series
Use on LV and MV systems
Basic metering with THD and min/max readings
Instantaneous rms values
Current (per phase and neutral)
Voltage (total, per phase L-L and L-N)
Frequency
Real, reactive, and apparent power (Total and per phase)
Signed, Four Quadrant
True Power Factor (Total and per phase)
Signed, Four Quadrant
Displacement PF (Total and per phase)
Signed, Four Quadrant
% Unbalanced I, V L-N, V L-L