PowerLogic™ PM5100 series user guide 
Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved
14
Technical Specifications
Energy Values*
Accumulated Active, Reactive and Apparent Energy
Received/Delivered; Net and absolute
Demand Values*
Current average
Present, Last, Predicted, Peak, and Peak 
Date Time
Active power
Present, Last, Predicted, Peak, and Peak 
Date Time
Reactive power
Present, Last, Predicted, Peak, and Peak 
Date Time
Apparent power
Present, Last, Predicted, Peak, and Peak 
Date Time
Demand calculation (Sliding, fixed and rolling block, thermal 
methods)
Synchronization of the measurement window to input, 
communication command or internal clock
Settable Demand intervals
Other Measurements*
Operating timer
Load timer
Alarm counters and alarm logs
Power Quality Measurements
THD, thd (Total Harmonic Distortion) I, V L-N, V L-L per phase
I, V L-N, V L-L
TDD (Total Demand Distortion)
Individual harmonics (odds)
15th
Data Recording
Min/max of instantaneous values, plus phase identification*
Alarms with 1s timestamp*
Min/max log
I/Os
Digital output
1
(kWh only)
Timestamp resolution in seconds
1
NOTE: 
*Stored in non-volatile memory
Electrical Characteristics
Type of measurement: True rms on three-phase 
(3P, 3P + N), zero blind
64 samples per cycle
Measurement accuracy
 IEC 61557-12 
1
PMD/[SD|SS]/K70/0.5
 Active Energy 
2
Class 0.5S as per IEC 62053-22 
 Reactive Energy 
2
Class 2S as per IEC 62053-23
 Active Power 
Class 0.5 as per IEC 61557-12 
1
 Reactive Power 
Class 2 as per IEC 61557-12 
1
 Apparent Power 
Class 0.5 as per IEC 61557-12 
1
 Current, Phase
Class 0.5 as per IEC 61557-12 
1
 Voltage, L-N
Class 0.5 as per IEC 61557-12 
1
 Frequency
Class 0.05 as per IEC 61557-12 
1