Chapter 4—Front panel display and meter setup
PowerLogic™  PM5100 series user guide
Related topics
Communications setup
After wiring the meter’s serial communications port, you can configure these ports so 
you can connect to the meter remotely and use device configuration software such as 
ION Setup to configure the meter.
Based on the reference model, the meter is equipped with the following communication 
ports:
Communication ports
Setting up serial communications
The Serial Port setup screen allows you to configure the meter’s RS-485 
communications port so you can use software to access the meter’s data or configure 
the meter remotely.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0000”), then press OK.
3. Press Comm.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
5. Modify the parameter as required, then press OK.
6. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
7. Press   to exit. Press Yes to save your changes.
Reference Models
Communication
PM5100
-
PM5110
RS-485
PM5111
RS-485
Serial communications setup menu tree
Communications setup parameters
Parameter
Values
Description
Protocol
Modbus
The communications format used to transmit data. The 
protocol must be the same for all devices in a 
communications loop.
Address
1 to 247
Set the address for this device. The address must be 
unique for each device in a communications loop. For 
Jbus protocol, set the device ID to 255.
Baud Rate
9600, 19200, 38400
Select the speed for data transmission. The baud rate 
must be the same for all devices in a communications 
loop.
Parity
Even, Odd, None
Select None if the parity bit is not used. The parity 
setting must be the same for all devices in a 
communications loop.