Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved
55
Setting Up 1-Second Alarms 
To set up a standard alarm:
1. Press 1-Sec. The 1-second 
alarm Select screen appears.
2. Press 
▼ 
and 
 to scroll 
through the list of standard 1–
second alarms.
3. Press Edit to select an alarm to 
be configured.
4. Press Edit to select Pickup 
Setpoint.
5. Press + to increment the active 
digit through the numerals 0-9.
6. Press 
 to enter the selected 
value for the active digit and 
move to the next digit to the left.
7. Continue until all values are 
selected, then press OK to 
enter the selected number for 
the pickup setpoint.
8. For power factor alarms (Lead 
PF, True; Lag PF, True; Lead 
PF, Disp; and Lag PF, Disp) 
press 
 to select PU Set Point 
Lead/Lag, then press Edit. For 
other alarms, skip to Step 11.
9. Press + and - to scroll between 
Lead and Lag.
10. Press OK to set the pickup set 
point lead or lag.
11. Press 
and follow Steps 4 to 
7 for Pickup Time Delay and 
Dropout Setpoint.
12. For power factor alarms, press 
to select DO Set Point 
Lead/Lag and follow Steps 10 
and 11. For other alarms, 
proceed to Step 14.
13. Press 
and follow Steps 4 to 
7 for Dropout Time Delay.
14. Press 
 to select Enable, then 
press Edit.
15. Press + and - to scroll between 
Yes and No.
16. Press OK to enable or disable 
the alarm.