Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved
57
Setting Up Unary Alarms
To set up unary alarms:
Viewing Alarm Activity and History
There are two types of alarm entries: primary and secondary. The primary entry identifies
the alarm. The secondary entries provide pickup and dropout information.
the alarm. The secondary entries provide pickup and dropout information.
The active alarm list holds 40 entries at a time. The list works as a circular buffer,
replacing old entries as new entries over 40 are entered into the alarm event queue. The
information in the alarm event queue reinitializes when the power meter resets.
replacing old entries as new entries over 40 are entered into the alarm event queue. The
information in the alarm event queue reinitializes when the power meter resets.
The alarm history log holds 40 entries. The log also works as a circular buffer, replacing
old entries with new entries. This information is nonvolatile.
old entries with new entries. This information is nonvolatile.
1. Press Unary. The unary alarm
Select screen appears.
2. Press
▼
and
▲
to scroll
through the list of unary alarms.
3. Press Edit to select an alarm to
be configured.
4. Press Edit to select Enable.
5. Press + and - to scroll between
Yes and No.
6. Press OK to enable or disable
the alarm.
7. Press
▼
to select Priority.
8. Press + and - to scroll through
priority options Low, None,
High, or Medium.
High, or Medium.
NOTE:
on page 53 for more
information.
information.
9. Press OK to set the priority.
10. Press
10. Press
▲
to save all alarms
selections and return to the
previous screen.
previous screen.
11. Press
▲
to save all unary
alarm selections.