Chapter 7—Alarms
© 2014 Schneider Electric All Rights Reserved
57
Setting Up Unary Alarms 
To set up unary alarms:
Viewing Alarm Activity and History
There are two types of alarm entries: primary and secondary. The primary entry identifies 
the alarm. The secondary entries provide pickup and dropout information.
The active alarm list holds 40 entries at a time. The list works as a circular buffer, 
replacing old entries as new entries over 40 are entered into the alarm event queue. The 
information in the alarm event queue reinitializes when the power meter resets.
The alarm history log holds 40 entries. The log also works as a circular buffer, replacing 
old entries with new entries. This information is nonvolatile.
1. Press Unary. The unary alarm 
Select screen appears.
2. Press 
▼ 
and 
 to scroll 
through the list of unary alarms.
3. Press Edit to select an alarm to 
be configured.
4. Press Edit to select Enable.
5. Press and to scroll between 
Yes and No.
6. Press OK to enable or disable 
the alarm.
7. Press 
 to select Priority.
8. Press and - to scroll through 
priority options Low, None, 
High, or Medium.
NOTE:
on page 53 for more 
information.
9. Press OK to set the priority.
10. Press 
 to save all alarms 
selections and return to the 
previous screen.
11. Press 
 to save all unary 
alarm selections.