Schneider Electric PM5100 Manual De Usuario

Descargar
Página de 96
PowerLogic™  PM5100 series user guide 
Chapter 10—Verifying accuracy
© 2014 Schneider Electric All Rights Reserved
75
Where:
EM = energy measured by the meter under test
ES = energy measured by the reference device or energy standard.
NOTE:
If accuracy verification reveals inaccuracies in your meter, they may be caused 
by typical sources of test errors. If there are no sources of test errors present, please 
contact your local Schneider Electric representative.
Energy pulsing considerations
The meter’s alarm / energy LED and digital outputs are capable of energy pulsing within 
the following limits:
The pulse rate depends on the voltage, current and PF of the input signal source, the 
number of phases, and the VT and CT ratios.
If Ptot is the instantaneous power (in kW) and K is the pulse constant (in pulses per 
k_h), then the pulse period is:
VT and CT considerations
The test points are always taken at the secondary side, regardless of whether VTs or 
CTs are used. Ptot is derived from the values of the voltage and current inputs at the 
secondary side, and takes into account the VT and CT ratios. 
If VTs and CTs are used, you must include their primary and secondary ratings in the 
equation. For example, in a balanced 3-phase Wye system with VTs and CTs:
Total power limit for alarm / energy LED
Given the maximum pulse constant (Kmax) you can enter is 9,999,999 pulses per kWh, 
and the maximum pulse frequency for the alarm / energy LED is 83 Hz, the maximum 
total power (Max Ptot) the alarm / energy LED’s energy pulsing circuitry can handle is 
29.88 Watts:
Total power limit for digital output
Given the maximum pulse constant (Kmax) you can enter is 9,999,999 pulses per kWh, 
and the maximum pulse frequency for the digital output is 25 Hz, the maximum total 
power (Max Ptot) the digital input’s energy pulsing circuitry can handle is 9 Watts:
Energy pulsing limits
Description
Alarm / energy LED
Digital output
Maximum pulse frequency
50 Hz
25 Hz
Minimum pulse constant
1 pulse per k_h
Maximum pulse constant
9,999,999 pulses per k_h
Pulse period (in seconds)
3600
K Ptot
--------------------
1
Pulse frequency (Hz)
---------------------------------------------------
=
=
Ptot
3 VLN
VT primary
VT secondary
---------------------------------
I
CT primary
CT
ondary
sec
----------------------------------- PF
1 kW
1000 W
-------------------
=
Maximum Ptot
3600 (Maximum pulse frequency)
Kmax
---------------------------------------------------------------------------------------
3600 83
9,999,999
------------------------
0.02988 kW
=
=
=