PowerLogic™  PM5100 series user guide 
Chapter 11—Meter resets
© 2014 Schneider Electric All Rights Reserved
77
Chapter 11—Meter resets
Reset commands clear the meter’s onboard data logs and related registers. Meter 
resets are typically performed after you make changes to the meter’s basic setup 
parameters (such as power system, frequency, or PT/CT settings), to clear invalid or 
obsolete data in preparation for putting the meter into active service.
The meter reset commands are grouped into two categories: Global Resets and Single 
Resets.
Front panel meter reset screens
To access the meter reset screens, navigate to Maint > Reset.
Global resets
Global resets allow you to clear all data of a particular type, such as all energy values or 
all minimum/maximum values.
Meter Initialization
 is a special command that clears the meter’s recorded logged data, 
counters and timers. It is common practice to initialize the meter after its configuration is 
completed, before adding it to an energy management system.
1. Navigate to Maint > Reset.
2. Move the cursor to point to Global Reset, then press Select.
3. Move the cursor to point to the parameter you want to reset, then press Reset.
4. Enter the reset password (default is “0000”), then press OK.
5. Press Yes to confirm the reset or No to cancel and return to the previous screen.
NOTICE
LOST DATA
Record all important data before performing meter resets.
Failure to follow these instructions can result in data loss.
Reset menu tree
Maint
Reset
Setup
Diag
Global reset options
Parameter
Description
Meter Initialization
Clears all data listed in this table (energy, demand, min/max values, 
counters, logs, timers, and input metering data).
Energies
Clears all accumulated energy values (kWh, kVARh, kVAh).
Demands
Clears all the demand registers.
Min/Max
Clears all the minimum and maximum registers.
Alarm Counts & Logs
Clears all the alarm counters and alarm logs.