Chapter 11—Meter resets
PowerLogic™  PM5100 series user guide
Single resets
Single resets allow you to clear data only in a specific register or register type.
1. Navigate to Maint > Reset.
2. Move the cursor to point to Single Reset, then press Select.
3. Move the cursor to point to the parameter you want to reset, then press Reset. If 
there are additional options for the parameter, press Select, move the cursor to 
point to the option you want, then press Reset.
4. Enter the reset password if prompted (default is “0000”), then press OK.
5. Press Yes to confirm the reset or No to cancel and return to the previous screen.
Single reset options
Parameter
Option
Description
Energy
Accumulated
Clears all accumulated energy values (kWh, 
kVARh, kVAh).
Demand
Power, Current
Select which demand registers to clear 
(power demand, current demand or input 
metering demand).
Alarms
Event Queue
Clears the alarm event queue register.
History Log
Clears the alarm history log.
Counters
All Alarm Counts, 
(various alarm 
counters) — see the 
next table
Select “Counters”, then select which counter 
to clear (choose all or individual alarm 
counters listed in the “Alarm counter options”  
table below).
Active Load Timer
Clears and restarts the load operation timer.
Alarm counter options
Alarm counter
Option
Description
Current
Over Current, Ph
Select which alarm counter register to reset from 
the current alarm condition counters.
Under Current, Ph
Over Current, N
Over Current, Gnd
Voltage
Over Voltage, L-L
Select which alarm counter register to reset from 
the voltage alarm condition counters.
Under Voltage, L-L
Over Voltage, L-N
Under Voltage, L-N
Over Voltage Unbal
Over Voltage THD
Phase Loss
Power
Over kW
Select which alarm counter register to reset from 
the power alarm condition counters.
Over kVAR
Over kVA
Power Factor
Lead PF, True
Select which alarm counter register to reset from 
the power factor alarm condition counters.
Lag PF, True
Lead PF, Disp
Lag PF, Disp
Demand
Over kW Dmd, Pres
Select which alarm counter register to reset from 
the demand alarm condition counters.
Over kW Dmd, Last
Over kW Dmd, Pred
Over kVAR Dmd, Pres
Over kVAR Dmd, Last
Over kVAR Dmd, Pred
Over kVA Dmd, Pres
Over kVA Dmd, Last
Over kVA Dmd, Pred