Chapter 3—Operation
21
Lock Resets Setup
Alarm Backlight Setup
Bar Graph Setup
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until LOCK is visible.
5. Press LOCK.
6. Select Y (yes) or N (no) to enable or disable 
resets for PK.DMD, ENERG, MN/MX, and 
METER.
7. Press OK.
8. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
9. Press YES to save the changes.
9'$< #=#7=>
 
+
?"@A
#7#)
!
P
LSD1
1020
0
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until BLINK is visible.
5. Press BLINK.
6. Enter ON or OFF.
7. Press OK.
8. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
9. Press YES to save the changes.
 
* *+>
PLS
D
110
215
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until BARGR is visible.
5. Press BARGR.
6. Press AMPS or PWR.
7. Select AUTO or MAN. If MAN is selected, press 
OK and enter the %CT*PT and KW (for PWR) 
or the %CT and A (for AMPS). 
8. Press OK.
9. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
10. Press YES to save the changes.
-)B)-C=$-9#
6
P
LSD1
1023
1