Chapter 3—Operation
3/2011
22
PQ Advanced Evaluation Setup
Power Demand Configuration Setup
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until PQADV is visible.
5. Press PQADV.
6. Select ON.
7. Press OK.
8. Change the nominal voltage (NOM V) value if 
desired (the default is 230).
9. Press OK to return to the SETUP MODE 
screen.
10. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
11. Press YES to save your changes and reset the 
power meter.
4 ;-
 
.
1. Perform steps 1 through 5 of the SETUP MODE 
Access procedure on page 11.
2. Press 
###:
 until ADVAN (advanced setup) is 
visible.
3. Press ADVAN.
4. Press 
###:
 until DMD is visible.
5. Press DMD (P-DMD, I-DMD).
6. Select the demand configuration. Choices are 
COMMS, RCOMM, CLOCK, RCLCK, IENGY, 
THERM, SLIDE, BLOCK, RBLCK, INPUT, and 
RINPUT.
7. Press OK. 
8. Enter the INTVL (interval) and press OK. 
9. Enter the SUB-I (sub-interval) and press OK. 
10. At the SETUP MODE screen, continue 
programming additional setup features or 
press
1;
 until you are asked to save changes.
11. Press YES to save the changes.