PowerLogic
TM
 Series 800 Power Meter
63230-500-225A2
Chapter 3—Operation
3/2011
24
Accumulated Demand Readings Reset
Minimum/Maximum Values Reset
Display Mode Change
1. Press 
###:
 to scroll through the Level 1 menu 
until you see MAINT.
2. Press MAINT.
3. Press RESET.
4. Press 
###:
 until DMD is visible.
5. Press DMD.
6. Enter the password (the default is 0000).
7. Press YES to reset the accumulated demand 
readings and to return to the RESET MODE 
screen.
>
!
<. F
<6F
<
<
<
P
LS
D
1102
81
1. Press 
###:
 to scroll through the Level 1 menu 
until you see MAINT.
2. Press MAINT.
3. Press RESET.
4. Press 
###:
 until MINMX is visible.
5. Press MINMX.
6. Enter the password (the default is 0000).
7. Press YES to reset the minimum/maximum 
values and to return to the RESET MODE 
screen.
"/>
!
P
LS
D
1102
82
1. Press 
###:
 to scroll through the Level 1 menu 
until you see MAINT.
2. Press MAINT.
3. Press RESET.
4. Press 
###:
 until MODE is visible.
5. Press MODE.
6. Press IEEE (default for Square D branded 
power meters) or IEC (default for Schneider 
Electric branded power meters) depending on 
the operating mode you want to use.
NOTE: Resetting the mode changes the menu 
labels, power factor conventions, and THD 
calculations to match the standard mode selected. 
To customize the mode changes, see the register 
list.