Schneider Electric PM870 Manual De Usuario

Descargar
Página de 122
© 2011 Schneider Electric. All Rights Reserved.
63230-500-225A2
PowerLogic
TM
 Series 800 Power Meter
3/2011
Chapter 7—Logging
63
Configure the Billing Log Logging Interval
The billing log can be configured to update every 10 to 1,440 minutes. The default logging 
interval is 60 minutes. To set the logging interval you can use PowerLogic software, or you 
can use the power meter to write the logging interval to register 3085 (see “Read and 
Write Registers”
 on page 26
).
Table 7–6: Billing Log Register List
Description
Number of 
Registers
Data Type
Register Number
Start Date/Time
3
D/T
Current D/T
Real Energy In
4
MOD10L4
1700
Reactive Energy In
4
MOD10L4
1704
Real Energy Out
4
MOD10L4
1708
Reactive Energy Out
4
MOD10L4
1712
Apparent Energy Total
4
MOD10L4
1724
Total PF
1
INT16
1163
3P Real Power Demand
1
INT16
2151
3P Apparent Power Demand
1
INT16
2181
 Refer to Appendix A for more information about data types.