Chapter 8—Waveform Capture
63
Chapter 8—Waveform Capture
Introduction
This section explains the waveform capture capabilities of the following Power Meter 
models:
PM850
PM870
See Table 8–1 for a summary of waveform capture features.
Waveform Capture
A waveform capture can be initiated manually or by an alarm trigger to analyze steady-
state or disturbance events. This waveform provides information about individual 
harmonics, which PowerLogic software calculates through the 63rd harmonic. It also 
calculates total harmonic distortion (THD) and other power quality parameters. 
NOTE: Disturbance waveform captures are available in the PM870 only.
In the PM850, the waveform capture records five individual three-cycle captures at 128 
samples per cycle simultaneously on all six metered channels. In the PM870, there is a 
range of one to five waveform captures, but the number of cycles captured varies based on 
the number of samples per cycle and the number of channels selected in your software. 
Use Figure 8–1 to determine the number of cycles captured.
NOTE: The number of cycles shown above are the total number of cycles allowed (pre-
event cycles + event cycles = total cycles).
Table 8–1: Waveform capture summary by model
Waveform Capture Feature
PM850
PM870
Number of waveform captures
5
5
Waveform initiated:
Manually
By alarm


Samples per cycle
128
Configurable*
Channels (1 to 6)
Configurable
Configurable*
Cycles
3
Configurable*
Precycles
1
Configurable*
Figure 8–1: PM870 Number of Cycles Captured
6
5
4
3
2
1
30
35
45
60
90
185
15
15
20
30
45
90
16              32              64              128
7
9
10
15
20
45
3
4
5
7
10
20
Number 
of 
Channels
Number of Samples per Cycle
P
LSD1
1033
3