Drive ratings
Single-phase supply voltage: 100…120 V 50/60 Hz
For three Phase Output 200/240 V motors
Single-phase supply voltage: 200…240 V 50/60 Hz
For three Phase Output 200/240 V motors 
Three-phase supply voltage: 200…240 V 50/60 Hz
For three Phase Output 200/240 V motors
(3) Size description
Motor
Line supply (input)
Drive (output)
Reference
(2)
Size
(3)
Power indicated 
on plate (1)
Maximum line current
Apparent
power
Power
dissipated
at nominal
current (1)
Nominal
current
In
Max. transient 
current for
at 100 V
at 120 V
60 s
2 s
kW
HP
A
A
kVA
W
A
A
A
0.18
0.25
6
5
1
18
1.4
2.1
2.3
ATV12H018F1
1C1
0.37
0.5
11.4
9.3
1.9
29
2.4
3.6
4
ATV12H037F1
1C1
0.75
1
18.9
15.7
3.3
48
4.2
6.3
6.9
ATV12H075F1
2C1
Motor
Line supply (input)
Drive (output)
Reference
(2)
Size
(3)
Power indicated 
on plate (1)
Maximum line current
Apparent
power
Power
dissipated
at nominal
current (1)
Nominal
current
In
Max. transient 
current for
at 200 V
at 240 V
60 s
2 s
kW
HP
A
A
kVA
W
A
A
A
0.18
0.25
3.4
2.8
1.2
18
1.4
2.1
2.3
ATV12H018M2
1C2
0.37
0.5
5.9
4.9
2
27
2.4
3.6
4
ATV12H037M2
1C2
0.55
0.75
8
6.7
2.8
34
3.5
5.3
5.8
ATV12H055M2
1C2
0.75
1
10.2
8.5
3.5
44
4.2
6.3
6.9
ATV12H075M2
1C2
1.5
2
17.8
14.9
6.2
72
7.5
11.2
12.4
ATV12HU15M2
2C2
2.2
3
24
20.2
8.4
93
10
15
16.5
ATV12HU22M2
2C2
Motor
Line supply (input)
Drive (output)
Reference
(2)
Size
(3)
Power indicated 
on plate (1)
Maximum line current 
Apparent
power
Power
dissipated
at nominal
current (1)
Nominal
current
In
Max. transient 
current for
at 200 V
at 240 V
60 s
2 s
kW
HP
A
A
kVA
W
A
A
A
0.18
0.25
2
1.7
0.7
16
1.4
2.1
2.3
ATV12H018M3
1C3
0.37
0.5
3.6
3
1.2
24
2.4
3.6
4
ATV12H037M3
1C3
0.75
1
6.3
5.3
2.2
41
4.2
6.3
6.9
ATV12H075M3
1C3
1.5
2
11.1
9.3
3.9
73
7.5
11.2
12.4
ATV12HU15M3
2F3
2.2
3
14.9
12.5
5.2
85
10
15
16.5
ATV12HU22M3
2F3
3
4
19
15.9
6.6
94
12.2
18.3
20.1
ATV12HU30M3
3F3
4
5.5
23.8
19.9
8.3
128
16.7
25
27.6
ATV12HU40M3
3F3
(1) These power ratings are for a switching frequency of 4 kHz, in continuous operation. The
switching frequency is adjustable from 2 to 16 kHz.
Above 4 kHz, the drive will reduce the switching frequency if an excessive temperature rise
occurs. The temperature rise is detected by a probe in the power module. Nonetheless,
derating should be applied to the nominal drive current if continuous operation above 4 kHz
is required:
• 10% derating for 8 kHz
• 20% derating for 12 kHz
• 30% derating for 16 kHz
(2) Reference description
example: ATV12HU15M3
ATV12: Altivar 12; 
H: product on heatsink; 
U15: drive power rating, 
see 
 parameter page 
M3: drive voltage rating, 
see 
 parameter page 
.
2
F
3
possible values 1
2
3
physical size 1
physical size 2
physical size 3
possible values F
C
Flat
Compact
1
2
3
100 V 1 phase
200 V 1 phase
200 V 3 phase
possible values