Short-circuit rating and branch circuit protection
Recommended fuse ratings for UL and CSA requirements. Components for use together in accordance with standard UL508 
1.  Types of enclosures that can be used: 1, 12, 3, 3R, 4, and 4X-all non-ventilated.
2.  The GV2P
pp
 self-protected manual combination starter must be used with the GV2GH7 insulating barrier to meet the UL 508 Type E 
rating.
3.  The GV3P
pp
 self-protected manual combination starter must be used with the GV3G66 insulating barrier and the GVAM11 auxiliary 
contact block to meet the UL 508 Type E rating.
4.  The line reactor is required when the ATV12 drive is used in a system with a current availability higher than the drive's SCCR design.
5.  When fuse type is not specified any Class J or CC can be used. If fuse manufacturer is not specified any fuse manufacturer can be used.
6.  Input withstand rating is that for which the product has been designed thermally. Installation on a supply greater than this level will 
require additional inductance to satisfy this level.
7.  Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuit protection. Branch circuit 
protection must be provided in accordance with the National Electrical Code and any additional local codes. This is dependant on the 
type of installation.
Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kiloAmperes,___Y___Volts maximum, when
protected by___Z1___with a maximum rating of___Z2___.
ATV12 Drive 
Short Circuit Current Ratings
1
Input 
Voltage
+10%/-15%
60 Hz
Y
(kW) (HP)
input
withstand
Rating (kA)
6
Reference
With QO Circuit Breaker
With GV2P/3P
With Fuses
QO QOB QOU
A
SCCR
(kA)
7
X
GV2P/3P
Type E 
2,3
SCCR 
(kA)
Fuses(A)
5
Z1, Z2
SCCR 
(kA)
Line 
Reactor
4
120 V,
1 phase
0.18
0.25
1
ATV12H018F1 yes
yes
yes
10
1
GV2P10
1
Ferraz HSJ (15)
1
-
0.37
0.5
1
ATV12p037F1 yes
yes
yes
20
1
GV2P14
1
Ferraz HSJ (25)
1
-
0.75
1
1
ATV12H075F1 yes
yes
yes
25
1
GV2P20
1
Ferraz HSJ (40)
1
-
240 V,
1 phase
0.18
0.25
1
ATV12H018M2 yes
yes
yes
10
1
GV2P08
1
Fast Acting 
Class CC 
Ferraz ATDR 
(7)
1
-
0.37
0.5
1
ATV12p037M2 yes
yes
yes
10
1
GV2P10
1
Ferraz HSJ (15)
1
-
0.55
0.75
1
ATV12p055M2 yes
yes
yes
15
1
GV2P14
1
Ferraz HSJ (25)
1
-
0.75
1
1
ATV12p075M2 yes
yes
yes
20
1
GV2P14
1
Ferraz HSJ (25)
1
-
1.5
2
1
ATV12HU15M2 no
no
yes
25
1
GV2P20
1
Ferraz HSJ (40)
1
-
2.2
3
1
ATV12HU22M2 no
no
yes
35
1
GV2P22
1
Ferraz HSJ (45)
1
-
240 V,
3 phase
0.18
0.25
5
ATV12H018M3 yes
yes
yes
10
5
GV2P07
5
Fast Acting 
Class CC 
Ferraz ATDR 
(7)
5
-
0.37
0.5
5
ATV12p037M3 yes
yes
yes
10
5
GV2P08
5
Fast Acting 
Class CC 
Ferraz ATDR 
(7)
5
-
0.75
1
5
ATV12p075M3 yes
yes
yes
15
5
GV2P14
5
Ferraz HSJ (15)
5
-
1.5
2
5
ATV12pU15M3 yes
yes
yes
15
5
GV2P16
5
Ferraz HSJ (25)
5
-
2.2
3
5
ATV12pU22M3 yes
yes
yes
25
5
GV2P20
5
Ferraz HSJ (25)
5
-
3
3
5
ATV12pU30M3 no
no
yes
30
5
GV2P21
5
Ferraz HSJ (40)
5
-
4
5
5
ATV12pU40M3 no
no
yes
40
5
GV2P22
Ferraz HSJ (45)
5
-
240 V,
3 phase
0.18
0.25
5
ATV12H018M3 yes
yes
yes
10
10
GV2P07
50
3
65
3%
0.37
0.5
5
ATV12p037M3 yes
yes
yes
10
10
GV2P08
50
8
65
3%
0.75
1
5
ATV12p075M3 yes
yes
yes
15
10
GV2P14
50
15
65
3%
1.5
2
5
ATV12pU15M3 yes
yes
yes
15
10
GV3P13
50
25
65
3%
2.2
3
5
ATV12pU22M3 yes
yes
yes
25
10
GV3P18
50
30
65
3%
3
3
5
ATV12pU30M3 no
no
yes
30
10
GV3P25
50
40
65
3%
4
5
5
ATV12pU40M3 no
no
yes
40
10
GV3P32
50
50
65
3%