Schneider Electric Altivar 12 Manual De Usuario
46
BBV28581 05/2010
How to control the drive locally
In factory settings "RUN" and the jog dial are inactive. To control the drive locally, adjust the following parameter:
set
set
to
AIU1
(Integrated display with jog dial).
LI assignment information
It is possible with ATV12 to use multi assignment function (ie:
and
on the same LI).
It is also possible on some functions to assign LIH (high) or LIl (low), which means that the assigned function will be activated to high (LIH)
or low level (LIl) of LI.
or low level (LIl) of LI.
Code
Name/Description
Adjustment range
Factory setting
nPr
M Rated Motor Power
NCV -5 to
NCV +2
NCV +2
According to drive
rating
rating
page
is set to
nPr
. If
nPr
is available
CoS
disappears.
Rated motor power given on the nameplate. Motors can range from five ratings lower up to two ratings
higher than the drive rating.. Performance is optimized when there is a maximum of one rating difference.
If
higher than the drive rating.. Performance is optimized when there is a maximum of one rating difference.
If
page
is set to 50Hz, the
nPr
unit will be kW,
otherwise it will be HP.
SCS
M Store customer parameter set
nO
nO
Str1
This function creates a backup of the present configuration:
v
Function inactive
v
Saves the current configuration in the drive memory.
SCS
automatically switches to
nO
as soon as the
save has been performed.
When a drive leaves the factory the current configuration and the backup configuration are both initialized
with the factory configuration.
with the factory configuration.
FCS
M Factory / recall customer parameter set
nO
nO
rEC1
InI
InI1
This function permits to restore a configuration.
v
Function inactive.
FCS
automatically changes to
nO
as soon as one of the following actions has been performed.
v
The current configuration becomes identical to the backup configuration previously saved by
SCS
.
FCS
automatically changes to
nO
as soon as this action has been performed.
rEC1
is only visible
if the backup has been carried out. If this value appears,
InI1
is not visible.
v
The current configuration becomes identical to the factory setting. If this value appears,
InI1
is not
visible.
v
The current configuration becomes identical to the backup configuration previously defined by SoMove
software. If this value appears, Ini and
software. If this value appears, Ini and
rEC1
are not visible.
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the current configuration is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
2 s
2 s
2 s