How to control the drive locally
In factory settings "RUN" and the jog dial are inactive. To control the drive locally, adjust the following parameter:
set 
  page 
 to 
AIU1
 (Integrated display with jog dial).
 LI assignment information
It is possible with ATV12 to use multi assignment function (ie: 
 and 
 on the same LI).
It is also possible on some functions to assign LIH (high) or LIl (low), which means that the assigned function will be activated to high (LIH)
or low level (LIl) of LI.
Code
Name/Description
Adjustment range
Factory setting
nPr
Rated Motor Power
NCV -5 to 
NCV +2
According to drive 
rating
Visible only if 
 page 
 is set to 
nPr
. If 
nPr
 is available 
CoS
 disappears.
Rated motor power given on the nameplate. Motors can range from five ratings lower up to two ratings 
higher than the drive rating.. Performance is optimized when there is a maximum of one rating difference.
If 
 page 
 is set to 50Hz, the 
nPr
 unit will be kW, 
otherwise it will be HP.
SCS
Store customer parameter set 
nO
nO
Str1
This function creates a backup of the present configuration:
v
Function inactive
v
Saves the current configuration in the drive memory. 
SCS
 automatically switches to 
nO
 as soon as the 
save has been performed.
When a drive leaves the factory the current configuration and the backup configuration are both initialized 
with the factory configuration.
FCS
Factory / recall customer parameter set
nO
nO
rEC1
InI
InI1
This function permits to restore a configuration.
v
Function inactive.
FCS
 automatically changes to 
nO
 as soon as one of the following actions has been performed.
v
The current configuration becomes identical to the backup configuration previously saved by 
SCS
FCS
 automatically changes to 
nO
 as soon as this action has been performed. 
rEC1
 is only visible 
if the backup has been carried out.  If this value appears, 
InI1
 is not visible.
v
The current configuration becomes identical to the factory setting. If this value appears, 
InI1
 is not 
visible.
v
The current configuration becomes identical to the backup configuration previously defined by SoMove 
software.  If this value appears, Ini and 
rEC1
 are not visible. 
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the current configuration is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
  To change the assignment of this parameter press the “ENT” key for 2 s.
2 s
2 s