Schneider Electric Altivar 12 Manual De Usuario

Descargar
Página de 133
BBV28581  05/2010
53
Code
Name/Description
Adjustment range
Factory setting
I_O-
Input Output menu 
(continued)
LO1-
LO1 Configuration menu (LO1-)
LO1
LO1 assignment
nO
Allows to adapt the logic output to the application need.
Same values as 
r1
.
 
See previous page. 
When 
MdE
 = 
YES
, output 
LO1
 is forced to 
PMP
 (See page 
).
LO1S
LO1 status (output active level)
POS
WARNING
LOSS OF CONTROL
When 
LO1S
 = 
nEG
 and 
LO1
 is set to 
FLt
, The output will be active when the drive will detect a fault. 
The drive status will not be detected if the wiring is damaged for any reason.
Do not select "
nEG
" unless you are sure that your signal will be present in any case.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
POS
nEG
v
Positive : hight activation level
v
Negative : low activation level
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-