BBV28581  05/2010
55
(1) In = nominal drive current
Code
Name/Description
Adjustment range
Factory setting
I_O-
Input Output menu 
(continued)
ULt
Application underload time delay
0 to 100 s
0 s
ULt
 can be adjusted between 0 and 100 s.
If the motor current undershoots the underload threshold 
LUL
 for longer than the adjustable time delay 
ULt
, the drive will stop running and display 
Underload detection is only active when the system is in steady state (speed reference reached).
A value of 0 will disable application underload detection. 
LUL
T
Application Underload threshold
20 to 100% of nCr
60%
Visible only if 
Application underload time delay
 
ULt
 is not set to 
0
. This parameter is used to detect an 
application underload condition on the motor. 
LUL
 can be adjusted 
between 20 and 100% of the nominal drive current.
FtU
T
Time delay before automatic start for the 
underload fault
0 to 6 min
0 min
If Atr = YES the drive restarts automatically after an underload fault 
ULF
 once this time delay has elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of 
Maximum restart time
 
tAr
 page 
 must 
exceed that of this parameter by at least one minute.
Visible only if 
Application underload time delay
 
ULt
 above is not set to 
nO
.
Ftd
T
Motor frequency threshold
0 to 400 Hz
50 or 60 Hz 
According to drive 
rating
Visible only if 
 page 
 or a 
 
 page 
 is set to 
FtA
.
Ctd
T
Motor current threshold
0 to 1.5 In (1)
InV
Visible only if 
 page 
 or a 
 
 page 
 is set to 
CtA
.
ttd
T
Motor thermal state threshold
0 to 118% of tHr
100%
Visible only if 
 page 
 is set to 
tSA
.
Trip threshold for motor thermal alarm (logic output or relay)
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
LUL
 +10%
Motor current
LUL
Drive stop on 
ULF
 
detected fault
ULt
ULt
(hysteresis)
t