BBV28581  05/2010
57
(1) In = nominal drive current
Code
Name/Description
Adjustment 
range
Factory setting
drC-
Motor control menu
bFr
Standard motor frequency
50 Hz
See page 
.
nPr
Rated motor power
NCV -5 to 
NCV +2
According to drive rating
See page 
.
CoS
Rated motor cos phi
0.5 to 1
According to drive rating
Visible only if 
 page 
 is set to 
CoS
. If 
 is 
available 
 disappears.
Motor nameplate power factor (pf).
Note: Do not confuse this with motor "Service Factor". Setting 
CoS
 to or very near to 1 may result in 
unsatisfactory motor operation. If the motor power factor is not indicated on the nameplate, leave this 
parameter at the factory default (approximately 0.80)
UnS
Rated motor voltage
100 to 480 V
230 V
Rated motor voltage given on the nameplate. If the line voltage is less than the rated motor voltage, 
UnS
 should be set to the value of the line voltage applied to the drive terminals.
nCr
Rated motor current
0.25 In to 1.5 In 
(1)
According to drive rating
Rated motor current given on the nameplate
nCr
 modifies 
 
 page 
.
FrS
Rated motor frequency
10 to 400 Hz
50 Hz
Rated motor frequency given on the nameplate.
The factory setting is 50 Hz, or preset to 60 Hz if 
 page 
 is set to 60 Hz.
nSP
Rated motor speed
0 to 24000 rpM
According to drive rating
Rated motor speed given on the nameplate.
tFr
Maximum frequency
10 to 400 Hz
60 Hz
tFr
 gives the upper value possible for 
 page 
The factory setting is 60 Hz, or preset to 72 Hz if 
 page 
 is set to 60 Hz.
Ctt
Motor control type
Std
PErF
Std
PUMP
Allows selection of the motor control type suitable for the application and the required performances.
v
Performance: SVCU; Sensorless vector control with internal speed loop based on voltage feedback 
calculation. For applications needing high performance during starting or operation. 
v
Standard: U/F 2 points (Volts/Hz) without internal speed loop
For simple applications that do not require high performance. Simple motor control law keeping a constant 
Voltage Frequency ratio, with a possible adjustment of the curve bottom.
This law is generally used for motors connected in paralell. Some specific applications with motors in 
paralell and high performance levels may require 
PErF
.
v
Pump: U²/F; dedicated to variable torque pump and fan applications that do not require high starting torque.