Schneider Electric Altivar 12 Manual De Usuario
![Schneider Electric](https://files.manualsbrain.com/attachments/984caf1d286e5e02d462a79fde1bf5fead2d9a5f/common/fit/150/50/91444bf287fb583af13341fc3281cd3c182bc046c845d04ce567acdbd94e/brand_logo.gif)
BBV28581 05/2010
77
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu
(continued)
PId-
PID menu
(continued)
PMP-
Pump sub-menu
tOL
M Application Overload time delay
0 to 100 s
0 s
See page
Visible only if
page
is not set to
nO
.
LOC
T
M Application Overload threshold
70 to 150% of nCr
90%
See page
Visible only if
Application Overload time delay
tOL
above is not set to
nO
.
FtO
T
M Time delay before automatic start for the
overload fault
overload fault
0 to 6 min
0 min
If
Atr
=
YES
the drive restarts automatically after an overload fault
OLC
once this time delay has
elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of
Maximum restart time
tAr
page
must
exceed that of this parameter by at least one minute.
Visible only if
Application Overload time delay
tOL
above is not set to
nO
.
ULt
M Application underload time delay
0 to 100 s
0 s
See page
Visible only if
page
is not set to
nO
.
LUL
T
M Application Underload threshold
20 to 100% of nCr
60%
See page
Visible only if
Application underload time delay
ULt
above is not set to
nO
.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-