Schneider Electric Altivar 12 Manual De Usuario

Descargar
Página de 133
BBV28581  05/2010
77
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu 
(continued)
PId-
PID menu 
(continued)
PMP-
Pump sub-menu
tOL
Application Overload time delay
0 to 100 s
0 s
See page 
Visible only if  
 pag
 is not set to 
nO
.
LOC
T
Application Overload threshold
70 to 150% of nCr
90%
See page 
Visible only if 
Application Overload time delay
 
tOL
 above is not set to 
nO
.
FtO
T
Time delay before automatic start for the 
overload fault
0 to 6 min
0 min
If 
Atr
 = 
YES
 the drive restarts automatically after an overload fault 
OLC
 once this time delay has 
elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of 
Maximum restart time
 
tAr
 page 
 must 
exceed that of this parameter by at least one minute.
Visible only if 
Application Overload time delay
 
tOL
 above is not set to 
nO
.
ULt
Application underload time delay
0 to 100 s
0 s
See page 
Visible only if  
 pag
 is not set to 
nO
.
LUL
T
Application Underload threshold
20 to 100% of nCr
60%
See page 
Visible only if 
Application underload time delay
 
ULt
 above is not set to 
nO
.
T