Schneider Electric Altivar 12 Manual De Usuario

Descargar
Página de 133
78
BBV28581  05/2010
Code
Name/Description
Adjustment range
Factory setting
FUn-
Function menu 
(continued)
PId-
PID menu 
(continued)
PMP-
Pump sub-menu 
(continued)
FtU
T
Time delay before automatic start for the 
underload fault
0 to 6 min
0 min
If 
Atr
 = 
YES
 the drive restarts automatically after an underload fault 
ULF
 once this time delay has 
elapsed.
Minimum time permitted between an underload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of 
Maximum restart time
 
tAr
 page 
 must 
exceed that of this parameter by at least one minute.
Visible only if 
Application underload time delay
 
ULt
 above is not set to 
nO
.
MdE
Selecting the operating mode
nO
v
nO
: single variable mode
v
YES
: single variable mode with auxiliary pump
When 
MdE
 = 
YES
, output LO1 is forced to 
PMP
 (see page 
).
Visible only if 
PID feedback assignment
 
PIF
 page 
 is not set to 
nO
.
FOn
T
Starting frequency of the auxiliary pump
0 to tFr
HSP
Above this frequency and after the pump starting time delay 
tOn
,
the auxiliary pump starts.
Visible only if 
Selecting the operating mode
 
MdE
 above is not set to 
nO
.
tOn
T
Time delay before starting the auxiliary 
pump
0 to 999.9 s
2 s
This time is necessary to avoid the effects of transient pressure fluctuation and thus prevent oscillation 
(pump starting/stopping).
Visible only if 
Selecting the operating mode
 
MdE
 above is not set to 
nO
.
rOn
T
Ramp for reaching the auxiliary pump 
nominal speed
0 to 999.9 s
2 s
Visible only if 
Selecting the operating mode
 
MdE
 above is not set to 
nO
.
FOF
T
Auxiliary pump stopping frequency
0 to tFr
0 Hz
Below this frequency and after the time delay for stopping the auxiliary pump 
tOF
, the pump stops.
Visible only if 
Selecting the operating mode
 
MdE
 above is not set to 
nO
.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-