Single variable with auxiliary pump mode - 1 variable speed pump (variable pump) and one fixed 
speed pump (auxiliary pump)
The auxiliary pump is controlled by the Altivar 12  via logic output LO.
Enter the values given on the motor rating plate in the Motor control menu drC
1st level adjustment parameters
ACC
 Acceleration: 0.1 s
dEC
 Deceleration: 0.1 s
LSP
 Low speed: 35 Hz
Analog input menu AIt
AI1t
 Scale of analog input AI1: 0-20 mA
Motor control menu drC
SLP
 Nominal motor slip: 0 Hz
FLG
 Frequency loop gain: 70%
UFr
 IR compensation: 0%
Application functions menu FUn
tCt
 2-wire type control: LEL
PI sub-menu
PIF
 Assignment of the PI function feedback: AI1
rPG
 PI regulator proportional gain: 5.00
rIG
 PI regulator integral gain: 8.00
rPI
 Internal PI regulator reference: 51%
rSL
 Restart error threshold: 42%
Pump sub-menu PMP
MdE
 Selecting the operating mode: YES
FOn
 Starting frequency of the auxiliary pump: 49 Hz
tOn
 Time delay before starting the auxiliary pump: 1 s
rOn
 Ramp for reaching the nominal speed of the auxiliary pump: 1 s
FOF
 Stopping frequency of the auxiliary pump: 39.6 Hz
tOF
 Time delay before the auxiliary pump stop command: 1 s
rOF
 Ramp for stopping the auxiliary pump: 1 s
nFd
 Zero flow detection: 1 min
FFd
 Zero flow detection activation threshold: 42 Hz
LFd
 Zero flow detection offset: 2 Hz
tLS
 Sleep threshold operating time: 5 s
SLE
 Sleep threshold offset: 3 Hz 
LO1
 Assignment as logic/analog output PMP
Automatic DC injection sub-menu AdC
AdC
 Automatic DC injection assignment: nO
Automatic restart function Atr
Atr
 Automatic restart: YES
Fault menu FLt
tUL
 Underload function time delay 5 s
LUL
 Underload threshold: 59%
FtU
 Time delay before automatic restart for the underload fault: 1 
 
Variable pump
ATV12
Fixed speed auxiliary pump
Pressure 
sensor
0-20 mA
4-20 mA
0+5 V
0+10 V