Schneider Electric Altivar 12 Manual De Usuario
BBV28581 05/2010
81
Single variable with auxiliary pump mode - 1 variable speed pump (variable pump) and one fixed
speed pump (auxiliary pump)
speed pump (auxiliary pump)
The auxiliary pump is controlled by the Altivar 12 via logic output LO.
Enter the values given on the motor rating plate in the Motor control menu drC
1st level adjustment parameters
1st level adjustment parameters
ACC
Acceleration: 0.1 s
dEC
Deceleration: 0.1 s
LSP
Low speed: 35 Hz
Analog input menu AIt
AI1t
Scale of analog input AI1: 0-20 mA
Motor control menu drC
SLP
Nominal motor slip: 0 Hz
FLG
Frequency loop gain: 70%
UFr
IR compensation: 0%
Application functions menu FUn
tCt
2-wire type control: LEL
PI sub-menu
PIF
Assignment of the PI function feedback: AI1
rPG
PI regulator proportional gain: 5.00
rIG
PI regulator integral gain: 8.00
rPI
Internal PI regulator reference: 51%
rSL
Restart error threshold: 42%
Pump sub-menu PMP
MdE
Selecting the operating mode: YES
FOn
Starting frequency of the auxiliary pump: 49 Hz
tOn
Time delay before starting the auxiliary pump: 1 s
rOn
Ramp for reaching the nominal speed of the auxiliary pump: 1 s
FOF
Stopping frequency of the auxiliary pump: 39.6 Hz
tOF
Time delay before the auxiliary pump stop command: 1 s
rOF
Ramp for stopping the auxiliary pump: 1 s
nFd
Zero flow detection: 1 min
FFd
Zero flow detection activation threshold: 42 Hz
LFd
Zero flow detection offset: 2 Hz
tLS
Sleep threshold operating time: 5 s
SLE
Sleep threshold offset: 3 Hz
LO1
Assignment as logic/analog output PMP
Automatic DC injection sub-menu AdC
AdC
Automatic DC injection assignment: nO
Automatic restart function Atr
Atr
Automatic restart: YES
Fault menu FLt
tUL
Underload function time delay 5 s
LUL
Underload threshold: 59%
FtU
Time delay before automatic restart for the underload fault: 1
Variable pump
ATV12
Fixed speed auxiliary pump
Pressure
sensor
0-20 mA
4-20 mA
0+5 V
0+10 V
sensor
0-20 mA
4-20 mA
0+5 V
0+10 V