Architecture of the pumping installation
Single variable mode - 1 single variable speed pump
Enter the values given on the motor rating plate in the Motor control menu drC
1st level adjustment parameters
ACC
 Acceleration: 0.7 s
dEC
 Deceleration: 0.7 s
LSP
 Low speed: 30 Hz
HSP
 High speed: 60 Hz
Analog input menu AIt
AI1t
 Scale of analog input AI1: 0-20 mA
Motor control menu drC
SLP
 Nominal motor slip: 0 Hz
FLG
 Frequency loop gain: 70%
UFr
 IR compensation: 0%
Application functions menu FUn
tCt
 2-wire type control: LEL
PI sub-menu
PIF
 Assignment of the PI function feedback: AI1
rPG
 PI regulator proportional gain: 5.00
rIG
 PI regulator integral gain: 8.00
rPI
 Internal PI regulator reference: 39%
rSL
 Restart error threshold: 40%
MPI
 Supervision of the PI regulator function: LFF
LPI
 PI feedback supervision threshold: 17%
tPI
 PI feedback supervision function time delay: 1 s
LFF
 Fallback speed: 50 Hz
Pump sub-menu PMP
nFd
 Zero flow detection: 1 min
FFd
 Zero flow detection activation threshold: 50 Hz
LFd
 Zero flow detection offset: 5 Hz
tLS
 Sleep threshold operating time: 3 s
SFS
 Quick start threshold: 25 Hz
SLE
 Sleep threshold offset: 10 Hz
Automatic DC injection sub-menu AdC
AdC
 Automatic DC injection assignment: nO
Automatic restart function Atr
Atr
 Automatic restart: YES 
Fault menu FLt
LOC
 Overload threshold: 11%
FtO
 Time delay before automatic start for the overload fault: 1
Ap0
 Frequency hysteresis reached: 2 kHz
 
Variable pump
ATV12
Pressure sensor
0-20 mA
4-20 mA
0+5 V
0+10 V