Schneider Electric Altivar 12 Manual De Usuario
94
BBV28581 05/2010
(1) In = nominal drive current
Code
Name/Description
Adjustment range
Factory setting
FLt-
Fault detection management menu
(continued)
tHt-
Motor thermal protection menu
ItH
T
M Motor thermal current
0.2 to 1.5 In (1)
According to drive
rating
rating
Current used for the motor thermal detection. Set ItH to the nominal current on the motor rating plate.
tHt
M Motor protection type
ACL
ACL
FCL
FCL
v
Self-ventilated
v
Motor-ventilated
OLL
M Overload fault management
YES
nO
YES
Type of stop in the event of a motor thermal fault.
v
Fault ignored
v
Freewheel stop
Setting
Setting
to
nO
inhibits the
page
.
CAUTION
RISK OF DAMAGE TO THE MOTOR
If
OLL
is set to
nO
, motor thermal protection is no longuer provided by the drive. Provide an alternative means
of thermal protection.
Failure to follow these instructions can result in equipment damage.
MtM
M Motor thermal state memo
nO
nO
YES
v
Motor thermal state not stored at power off.
v
Motor thermal state is stored at power off.
FLt-
Fault detection management menu
(continued)
OPL
M Output Phase loss
YES
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
If
OPL
is set to
nO
, loss of cable is not detected. Provide an alternative means of thermal protection.
Check this action will not endanger personnel or equipment in any way
Failure to follow these instructions will result in death or serious injury.
nO
YES
v
Function inactive
v
Tripping on OPF1 (1 phase loss) or OPF2 (3 phase loss) fault with freewheel stop.
IPL
M Input Phase loss
According to
drive rating
drive rating
nO
YES
This parameter is only accessible in this menu on 3-phases drives.
v
Fault ignored. To be used when the drive is supplied via a single phase supply.
v
Fault with freewheel stop.
If one phase disappears, the drive switches to fault mode Input Phase loss
If one phase disappears, the drive switches to fault mode Input Phase loss
but if 2 or 3 phases
disappear, the drive continues to operate until it trips on an undervoltage fault.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-