96
BBV28581 05/2010
Code
Name/Description
Adjustment range
Factory setting
FLt-
Fault detection management menu
(continued)
SLL
M Modbus fault management
YES
nO
YES
Behavior of the drive in the event of a communication fault with integrated Modbus.
v
Fault ignored
v
Freewheel stop
WARNING
LOSS OF CONTROL
If
Modbus fault mgt
SLL
is set to
n0
, communication control will be inhibited. For safety reasons, inhibition of
communication fault should only be used for adjustment or special applications purpose.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
drn
M Degraded line supply operation
nO
CAUTION
RISK OF DAMAGE TO THE DRIVE
When Derated operation = Yes, use a line choke.
Failure to follow these instructions can result in equipment damage.
nO
YES
Lowers the tripping threshold of the USF fault to operate on a line supply down to 50% of nominal line
voltage. In this case, the performance of the drive cannot be guaranteed
voltage. In this case, the performance of the drive cannot be guaranteed
v
nO
v
Yes
rPr
T
nO
FtH
M Reset power run
nO
This reset will initialize the settings located on
MOn
section, menu
MAI-
, page
v
nO
v
Reset fan time display
To change the assignment of this parameter press the “ENT” key for 2 s.
T
Parameter that can be modified during operation or when stopped.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s