Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
 48049-136-05
Appendix A—Register List
Rev. 01, 07/2012
© 1999–2012 Schneider Electric All Rights Reserved
36-EN
ENGLISH
Appendix A—Register List
List of Registers
The quantities are listed in alphabetical order 
according to the SMS topic name. 
NOTE: A system scan rate of 500 ms or greater 
is recommended to minimize communications 
timeout issues.
This is an abbreviated list of registers. For a 
complete list of registers, contact your local 
sales office. 
To access available registers, the following address scheme applies.
Module
Module Name
Equation
Address Range
BCM
Circuit Breaker Communication Module --
1–47
CCM
Cradle Communication Module
BCM + 50
51–97
PM
Protection Module (Internal to trip unit)
BCM + 100
101–147
MM
Meter Module (Internal to trip unit)
BCM + 200
201–247
Table 10:
Register List
SMS Topic Name User Description
Number of
Registers
*
Register*
Module*
Units
Scale/Bitmask
810DBrkrStatus
Circuit Breaker Status
1
661
BCM
Bit 0; ON = closed, OFF = open
810DBrkrTripStat
Circuit Breaker Trip Unit Status
1
661
BCM
Bit 2; ON = tripped, OFF = not tripped
BCM_SN
BCM Serial Number
4
516
BCM
ASCII text
BkrPos
Circuit Breaker Position
1
661
CCM
Bit 8 = disconnected
Bit 9 = connected
Bit 10 = test position
DT_3Regs
Device Clock Date/Time
3
679
BCM
3-register date/time format
EnableCloseBkr
Remote Closing Enabled
1
669
BCM
Bit 2; ON = enabled, OFF = not enabled
EnableOpenBkr
Remote Opening Enabled
1
669
BCM
Bit 1; ON = enabled, OFF = not enabled
EnableRemCtrl
Remote Control Enabled
1
669
BCM
Bit 3; ON = auto (enabled), 
OFF = manual (not enabled)
IA
Current A
1
8821
PM
A
Unity
IA_PCT
Current A % Load
1
8837
PM
%
Unity
IB
Current B
1
8822
PM
A
Unity
IB_PCT
Current B % Load
1
8838
PM
%
Unity
IC
Current C
1
8823
PM
A
Unity
IC_PCT
Current C % Load
1
8839
PM
%
Unity
IG
Current G
1
8825
PM
A
Unity
IG_PCT
Current G % Load
1
8841
PM
%
Unity
IG_PCT_VIGI
Current G (VIGI) % Load
1
8842
PM
%
Hundredths
IG_VIGI
Current G (VIGI)
1
8826
PM
A
Thousandths
IMax
Current Max Present
1
8820
PM
A
Unity
IN
Current N
1
8824
PM
A
Unity
IN_PCT
Current N % Load
1
8840
PM
%
Unity
LDPUValue
Long Delay Pickup Value
2
8756
PM
A
Modulo 10,000 format
**
MaxIA
Max Current A
1
8827
PM
A
Unity
MaxIB
Max Current B
1
8828
PM
A
Unity
MaxIC
Max Current C
1
8829
PM
A
Unity
MaxIG
Max Current G
1
8831
PM
A
Unity
MaxIG_VIGI
Max Current G (VIGI)
1
8832
PM
A
Thousandths
MaxIN
Max Current N
1
8830
PM
A
Unity
NominalCurrent
Circuit Breaker Nominal Current
1
8750
PM
A
Unity
ReadyToClose
Circuit Breaker Ready to Close
1
661
BCM
Bit 5; ON = yes, OFF = no
Continued on next page