Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic Trip Units
Rev. 01, 07/2012
Appendix A—Register List
© 1999–2012 Schneider Electric All Rights Reserved
37-EN
EN
G
L
ISH
TU_BATT_PCT
Trip Unit % Battery
1
8843
PM
%
Unity
TU_SN
Trip Unit Serial Number
4
8700
PM
ASCII text
TUCommStatus
Trip Unit Internal Comms Status
1
552
BCM
Bit 11; ON = not responding, OFF = OK
*
For register entries that are not listed, please refer to the Micrologic device type register list. Contact your local sales office.
BCM = Circuit breaker communication module. CCM = Cradle communication module. PM = Trip unit protection module.
3-register date/time format: register 1: month (byte 1) = 1–12, day (byte 2) = 1–31; register 2: year (byte 1) = 0–199 (add to 1900 to determine the actual year), hour 
(byte 2) = 0–23; register 3: minutes (byte 1) = 0–59, seconds (byte 2) = 0–59. Note: Bits 14 and 15 of the month/day register must be masked.
**
Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = –9,999 to +9,999). Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] 
+ R1. Range is zero to 9,999,999,999,999,999.