Honeywell W7750A Manual De Usuario

Descargar
Página de 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
57
74-2958—1
DestBypass -
Has possible states: Bypass On, 
Bypass Off or Not Assigned (not active). 
This input places the controller in an 
untimed bypass state or turns off the 
bypass mode. This source is second in 
priority to DestManOcc under the same 
arbitration schemes mentioned above.
Override Button -The wall module Override pushbutton 
can command status of Bypass, 
Continuous Unoccupied and Not 
Assigned. This source has the lowest 
priority status in the above mentioned 
schemes. The above mention sources 
of override must be either Not Assigned 
or Off before the Override pushbutton 
affects the manual override status in the 
Network Wins scheme. All actions, in 
this case, taken from the Override 
pushbutton are locked out.
Bypass status is a controller-timed 
event whose duration is set in BypTime. 
Upon expiration of the timer, the status 
returns to Not Assigned. The status of 
this input can be overridden with the 
receipt of Not Assigned from 
DestManOcc. This, in effect, cancels a 
timed bypass or a continuous 
unoccupied mode.
The Override pushbutton can be 
configured as Normal (all of the above 
mentioned states are possible), Bypass 
Only (Bypass and Not Assigned only) or 
None (effectively Disabling the Override 
pushbutton).
TIME CLOCK (Occ_Time_Clock)
OccTimeClock is the state of the digital input configured and 
wired to a time clock. When the digital input is detected to be 
Closed (Occupied), the scheduled occupancy will be 
OC_OCCUPIED. If the detected state of the digital input is 
Open (Unoccupied), then the scheduled occupancy will be 
OC_UNOCCUPIED. If the Occ_Time_Clock is not configured, 
then either the DestSchedOcc network input received from a 
central control or the time clock that is broadcast from a 
Sched_Master configured W7750, controls the occupied 
mode.
SCHEDULE MASTER (Sched_Master)
Sched_Master is the state of a digital input that is configured 
and wired to the W7750. If the Sched_Master input is closed 
(input shorted), the node is the schedule master and the state 
of the locally connected time clock will be broadcast out over 
the L
ON
W
ORKS
 Bus to the other W7750 controllers. If the 
Sched_Master input is open, then the node is not a schedule 
master and the local time clock will not be sent out over the 
L
ON
W
ORKS
 Bus even if the time clock input is configured. 
However, the DestSchedOcc network input received from a 
central control has a higher priority than the local time clock, 
and therefore overrides the local time clock. The W7750 
controllers automatically bind without the need for a 
configuration tool.
SETPOINT RAMPING
The W7750 Controller incorporates a ramping feature that 
gradually changes the space setpoints between occupancy 
modes. This feature is only operational if the network variable 
inputs DestSchedOcc, TodEventNext, and Time Until Next 
Change Of State (TUNCOS) are being used to change the 
W7750 Occupancy mode. The applicable Setpoints are 
OaTempMinHtRamp, OaTempMaxHtRamp, MinHtRamp and 
MaxHtRamp (for HEAT mode operation), and 
OaTempMinClRamp, OaTempMaxClRamp, MinClRamp and 
MaxClRamp (for the COOL mode operation). See Fig. 46 for a 
pictorial representation of how these setpoints interact.
During recovery operation, the setpoint changes at a rate in 
degrees per hour depending on the outdoor air temperature. If 
there is no outdoor air temperature sensor available, then 
MinHtRamp is used as the recovery rate.
Fig. 46. Setpoint ramping parameters with ramp rate 
calculation.
NOTE:
Recovery ramping applies between scheduled 
heating or cooling setpoint changes from 
UNOCCUPIED to STANDBY, UNOCCUPIED to 
OCCUPIED, and STANDBY to OCCUPIED. 
Scheduled setpoint changes from OCCUPIED to 
UNOCCUPIED or OCCUPIED to STANDBY do not 
use a ramped setpoint but instead use a step change 
in setpoint. Recovery ramps begin before the next 
scheduled occupancy time and are ramped from the 
setpoint for the existing scheduled occupancy state 
to the setpoint for the next occupancy state.
RECOVERY RAMPING FOR HEAT PUMP SYSTEMS
When the node is controlling heat pump equipment, during the 
recovery ramps, the heating setpoint is split into a heat pump 
setpoint (for compressors) and an auxiliary heat setpoint (for 
auxiliary heat stages). The heat pump setpoint is a step 
change at the recovery time prior to the OCCUPIED time. 
Recovery time is computed from the configured heat recovery 
ramp rate. The recovery time is calculated:
Recovery time = (OCC setpoint - current setpoint)/ramp rate
See Fig. 47 for the various setpoints.
HEAT RECOVERY 
RAMP RATE
(DEGREES/HOUR)
MaxHtRam
MinHtRam
OaTempMinHtRa
OaTempMaxHtRam
OUTDOOR AIR
TEMPERATURE
M10109