Honeywell W7750A Manual De Usuario

Descargar
Página de 116
EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
74-2958—1
58
Fig. 47. Setpoint ramping parameters with setpoint 
calculation.
During the COOL recovery period, the setpoint changes at a 
rate in degrees per hour relative to the outdoor air 
temperature. If there is no outdoor air temperature sensor 
available, the MinClRamp is used as the recovery rate.
See Fig. 48 for the various setpoints.
Fig. 48. Setpoint ramping parameters with ramp rate 
calculation.
NOTES: The setpoint used during the COOL recovery period 
is similar to the heat mode in Fig. 46, except the 
slope of the line reverses for cooling.
Recovery ramping applies between scheduled heat-
ing or cooling setpoint changes from UNOCCUPIED 
to STANDBY, UNOCCUPIED to OCCUPIED, and 
STANDBY to OCCUPIED. Scheduled setpoint 
changes from OCCUPIED to UNOCCUPIED or 
OCCUPIED to STANDBY do not use a ramped set-
point, but instead, use a step change in setpoint. 
Recovery ramps begin before the next scheduled 
occupancy time and are ramped from the setpoint for 
the existing scheduled occupancy state to the set-
point for the next occupancy state.
FAN OPERATION
The W7750 supply fan can be controlled in one of two 
different ways. In Continuous Fan mode, the fan runs 
whenever the controller is in Occupied mode. When in 
Standby or Unoccupied modes, the fan cycles on with a call 
for cooling (or heating if the FanOnHtMode parameter is set). 
In Intermittent Fan mode, the fan cycles on with a call for 
cooling (or heating if the FanOnHtMode parameter is set), and 
cycles off when the space temperature control is satisfied.
The fan control supports an optional (Proof of Air Flow) digital 
input, that allows monitoring of the supply fans status. If the 
fan is commanded on, the Proof of Air Flow digital input is 
checked up to three times to verify that the fan is running after 
an initial delay of FanOnDelay seconds (user-settable). If the 
fan fails to start the CVAHU must be reset by first cycling 
CVAHU power. If this does not work, set DestManMode to 
Manual and then back to Enable. After a reset the application 
restarts—all outputs switch off and auto control is enabled.
Also, the W7750 Controller provides fan-run-on operation that 
keeps the fan running for a short time after heating or cooling 
shuts off. The amount of time that the fan continues to run is 
set in FanRunOnHeat for heating mode and FanRunOnCool 
for cooling mode.
WINDOW SENSOR (StatusWndw)
The digital input for a window contact provides the algorithm 
with a means to disable its temperature control activities if 
someone has opened a window or door in the room. When a 
window is detected to be Open (digital input contacts Open 
equals window open), the normal temperature control is 
disabled, and the W7750 Controller enters the Freeze Protect 
mode. Freeze Protect mode sets the space setpoint to 46.4 °F 
(8°C) and brings on the fan and heat if the space temperature 
falls below this setpoint. Normal temperature control resumes 
on window closure. The Window sensor signal can also be a 
network input from another L
ON
W
ORKS
 Bus device, so that no 
physical sensor is required at the receiving W7750 Controller.
SMOKE CONTROL
The Excel 10 W7750 Controller supports three smoke-related 
control strategies:
1.
Emergency Shutdown (all outputs off).
2.
Depressurize (fan on, outdoor air damper closed).
3.
Pressurize (fan on, outdoor air damper open).
The controller is placed in one of these three control states 
whenever the W7750 mode becomes 
SMOKE_EMERGENCY, which can be initiated via a network 
command (DestEmergCmd) or from a local (physically 
connected) smoke detector digital input. When in 
SMOKE_EMERGENCY mode, the W7750 Controller uses the 
control strategy found in SmkCtlMode (one of the three listed 
above), and the normal temperature control function is 
disabled. If a W7750 local smoke detector trips, the SrcEmerg 
network variable (for other L
ON
W
ORKS
 Bus devices to receive) 
is set to the Emergency state.
DEMAND LIMIT CONTROL (DLC)
When The L
ON
W
ORKS
 Bus network receives a high-electrical-
demand signal, the controller applies a DlcBumpTemp amount 
to the current actual space temperature setpoint value. The 
setpoint is always adjusted in the energy-saving direction. 
This means that if the W7750 Controller is in Cooling mode, 
the DLC offset bumps the control point up, and when in 
Heating mode, bumps the control point down.
OCC setpoint
UN_OCC setpoint
OR
STANDBY setpoint
M10110
AUX HEAT
SETPOINT
HEAT PUMP
SETPOINT
(FOR COMPRESSORS)
RECOVERY TIME
OCCUPIED TIME
COOL RECOVERY 
RAMP RATE
(DEGREES/HOUR)
MaxClRam
MinClRam
OaTempMinClRa
OaTempMaxClRam
OUTDOOR AIR
TEMPERATURE
M10111