Bradford-White Corp Copper Brute II Hydronic Boiler Manual De Usuario

Descargar
Página de 64
Page 13
COPPER BRUTE II (500 - 2000)
DISTANCE FROM GAS METER
OR LAST STAGE REGULATOR
SIZE AND
GAS TYPE
 
0-100' 0-31m 
100-200' 31-61m 
200-300' 61-91m
500 natural
 
1-1/2" 
3.8cm
 
2" 
5.1cm
 
2" 
5.1cm
500 propane 
1" 
2.5cm
 
1-1/2" 
3.8cm
 
1-1/2" 
3.8cm
750 natural
 
2" 
5.1cm
 
2" 
5.1cm
 
2-1/2" 
6.4cm
750 propane 
1-1/2" 
3.8cm
 
1-1/2" 
3.8cm
 
2" 
5.1cm
1000 natural
 
2" 
5.1cm
 
2-1/2" 
6.4cm
 
3" 
7.6cm
1000 propane 
1-1/2" 
3.8cm
 
2" 
5.1cm
 
2-1/2" 
6.4cm
1250 natural
 
2-1/2" 
6.4cm
 
2-1/2" 
6.4cm
 
3" 
7.6cm
1250 propane 
2" 
5.1cm
 
2" 
5.1cm
 
2-1/2" 
6.4cm
1500 natural
 
2-1/2" 
6.4cm
 
3" 
7.6cm
 
3" 
7.6cm
1500 propane 
2" 
5.1cm
 
2-1/2" 
6.4cm
 
2-1/2" 
6.4cm
1750 natural
 
2-1/2" 
6.4cm
 
3" 
7.6cm
 
3" 
7.6cm
1750 propane 
2" 
5.1cm
 
2-1/2" 
6.4cm
 
2-1/2" 
6.4cm
2000 natural
 
3" 
7.6cm
 
3" 
7.6cm
 
3-1/2" 
8.9cm
2000 propane 
2-1/2" 
6.4cm
 
2-1/2" 
6.4cm
 
3" 
7.6cm
Notes:
1. These figures are based on 1/2" (0.12kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing
.
Table 7. Gas Piping Size.
SECTION 3. 
Gas Supply and Piping
3.1  Gas Supply and Piping
Gas piping should be supported by suitable 
hangers or floor stands, not by the appliance.
The Copper Brute II’s gas train allows the user to 
pipe the gas from either the right side or the left side 
of the unit. As shipped, the right side of the gas train is 
capped off, and there is a manual valve on the left side. 
If desired, the manual valve on the left side of the gas 
train may be moved to the right side, and the cap on 
the right side may be moved to the left. 
Review the following instructions before 
proceeding with the installation.
1.  Verify that the appliance is fitted for the proper 
type of gas by checking the rating plate. Copper 
Brute II appliances are equipped to operate at 
elevations up to 10,000 feet (3050m). Copper 
Brute II appliances may be adjusted to operate 
properly at altitudes above 2500 feet (
see Section 
6.5.2
) and the input will be reduced if the heating 
value of the gas supply is below sea level values.
2.  The maximum inlet gas pressure must not 
exceed 13" w.c. (3.2kPa). The minimum inlet gas 
pressure is 5" w.c. (1.2kPa).
3.  Refer to 
Table 7
, size supply.
4.  Run gas supply line in accordance with all 
applicable codes.
5.  Locate and install manual shutoff valves in 
accordance with state and local requirements.
6.  A sediment trap must be provided upstream of 
the gas controls.
7.  All threaded joints should be coated with 
piping compound resistant to action of liquefied 
petroleum gas.
8.  The appliance and its individual shutoff valve 
must be disconnected from the gas supply piping 
during any pressure testing of that system at test 
pressures in excess of 1/2 PSIG (3.45kpa).
9.  The unit must be isolated from the gas supply 
system by closing its individual manual shutoff 
valve during any pressure testing of the gas 
supply piping system at test pressures equal to or 
less than 1/2 PSIG (3.45kpa).
10.  The appliance and its gas connection must be 
leak tested before placing it in operation.
11.  Purge all air from gas lines.
 WARNING
Do not use open flame to check for leaks. An open 
flame could lead to explosion, which could result in 
property damage, serious injury or death.
NOTE
: The Copper Brute II appliance and all other 
gas appliances sharing the gas supply line must be 
firing at maximum capacity to properly measure the 
inlet supply pressure. The pressure can be measured 
at the supply pressure port on the gas valve. Low 
gas pressure could be an indication of an undersized 
gas meter, undersized gas supply lines and/or an 
obstructed gas supply line.