Bradford-White Corp Copper Brute II Hydronic Boiler Manual De Usuario

Descargar
Página de 64
Page 14
 
B
RADFORD
 W
HITE
 C
ORP.
  
20°F 25°F 30°F 35°F
 
SIZE
 
flow 
H/L 
flow 
H/L 
flow 
H/L 
flow 
H/L
  
gpm  feet  gpm  feet  gpm  feet  gpm  feet
 500  43 1.7 34 1.1 28 0.9 24 0.7
 750  64 3.3 51 2.3 43 1.7 36 1.2
 1000  85 5.0 68 3.6 57 3.1 49 2.2
 1250  106 8.1 85 6.1 71 4.7 61 3.4
 1500  128 
10.0 
102 7.2 85 5.5 73 4.2
 1750  N/R 
N/R 119 
10.5 99 8.4 85 5.8
 2000  N/R N/R 136 12.5 113 10.4  97  8.3
 Metric Equivalent
 
  11°C 14°C 17°C 19°C
 
SIZE
 
flow
H/L
flow
H/L
flow
H/L
flow
H/L
  
lpm m lpm m lpm m lpm m
  500  161 0.5 129 0.3 107 0.3  92  0.2
  750  241 1.0 193 0.7 161 0.5 138 0.4
 1000  321 1.5 257 1.1 214 0.9 184 0.7
 1250  401 2.5 322 1.9 269 1.4 231 1.0
 1500  483 3.0 386 2.2 322 1.7 276 1.3
 1750
N/R  N/R  451  3.2  375  2.6  322  1.8
 2000
N/R  N/R  515  3.8  429  3.2  368  2.5
Notes: gpm = gallons per minute, lpm = liters per minute, 
H/L = headloss, ft = headloss in feet, m = headloss in meters.
Maximum temperature rise is 35°F (19°C), as shown. 
Headloss is for boiler’s heat exchanger only. 
N/R = not recommended.
Table 8. Water Flow Requirements - BWCH.
SECTION 4A.
Water Connections —  
Copper Brute II Boiler
4A.1 Heating System Piping:  
Hot Supply Connections — Boiler
NOTE: This appliance must be installed in a closed 
pressure system with a minimum of 12 psi (82.7kPa) 
static pressure at the boiler.
Hot water piping should be supported by suitable 
hangers or floor stands. Do not support piping with 
this appliance. Due to expansion and contraction of 
copper pipe, consideration should be given to the type 
of hangers used. Rigid hangers may transmit noise 
through the system resulting from the piping sliding in 
the hangers. It is recommended that padding be used 
when rigid hangers are installed. Maintain 1" clearance 
to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) 
to a drain or in a manner to prevent injury in the event 
of pressure relief. Install an air purger, an air vent, 
a diaphragm-type expansion tank, and a hydronic 
flow check in the system supply loop. Minimum fill 
pressure must be 12psig (82.7kPa). Install shutoff 
valves where required by code.
Suggested piping diagrams are shown in 
Figures 
4 through 8.
 These diagrams are meant only as a guide. 
Components required by local codes must be properly 
installed.
Note the recommended location of the 
temperature sensor on the diagrams; you must provide 
a location for the additional sensor shipped with 
the Copper Brute II. This sensor may be strapped 
onto pipe from 1" to 4" diameter, or inserted into an 
immersion well.
4A.2 Cold Water Make-Up — Boiler
1.  Connect the cold water supply to the inlet 
connection of an automatic fill valve.
2.  Install a suitable back flow preventer between the 
automatic fill valve and the cold water supply.
3.  Install shut off valves where required.
NOTE: 
The boiler, when used in connection with a 
refrigeration system, must be installed so the chilled 
medium is piped in parallel with the boiler with 
appropriate valves to prevent the chilled medium from 
entering the boiler.
The boiler piping system of a hot water heating 
boiler connected to heating coils located in air 
handling appliances where they may be exposed to 
refrigerated air circulation must be equipped with flow 
control valves or other automatic means to prevent 
gravity circulation of the boiler water during the 
cooling cycle.
A boiler installed above radiation level, or as 
required by the authority having jurisdiction, must be 
provided with a low water cutoff device either as a part 
of the boiler or at the time of boiler installation.
4A.3 Water Flow Requirements — Boiler
A hydronic heating (closed loop) application 
re-circulates the same fluid in the piping system. As a 
result, no new minerals or oxygen is introduced into 
the system. To ensure a proper operating temperature 
leading to long boiler life, a flow rate has been 
established based on the fluid temperature rise for this 
specific size boiler.
Pump-mounted boilers can be ordered for use in 
primary secondary piping systems. The pumps used 
are sized for the headloss through the heater, plus 30 
feet (9.1m) of full-sized piping (same size as boiler 
outlet) and a normal number of fittings. 
Table 8
 specifies water flow rates for boilers, 
which will enable the user to size a pump. The 
headloss shown is for the heater only, and the user 
will need to add the headloss of the system piping to 
properly size the pump.
The minimum inlet water temperature for the 
Copper Brute II is 120°F (49°C) to avoid condensing 
on the copper coils.
4A.4 Freeze Protection — Boiler
Boiler installations are not recommended in 
areas where the danger of freezing exists unless proper