Bradford-White Corp Copper Brute II Hydronic Boiler Manual De Usuario

Descargar
Página de 64
Page 43
COPPER BRUTE II (500 - 2000)
Figure 29. Temperature Control Min & Max.
minimum amount of time before turning on the next 
stage. After the minimum time delay between stages 
has expired, the control examines the control error to 
determine when the next stage is to fire. The control 
error is determined using PID logic.
Proportional compares the actual operating 
sensor temperature to the boiler target temperature. 
The colder the temperature, the sooner the next stage 
is turned on.
Integral compares the actual operating sensor 
temperature to the boiler target temperature over a 
period of time.
Derivative determines how fast or slow the 
operating sensor temperature is changing. If the 
temperature is increasing slowly, the next stage is 
turned on sooner. If the temperature is increasing 
quickly, the next stage is turned on later, if at all.
Boiler Mass (
BOIL MASS– The boiler mass 
setting allows the installer to adjust the control to the 
thermal mass of different types of heat sources used. 
The boiler mass setting automatically determines the 
interstage differential, interstage delay on, interstage 
delay off, minimum on time and minimum off time of 
the stages when PID staging is used. A higher thermal 
mass setting provides slower staging, while a lower 
thermal mass setting provides faster staging. Copper 
Brute II boilers and water heaters are low-mass 
appliances, and therefore, should be used with the 
lower thermal mass setting. Set BOIL MASS to “1”.
6.4.3  Boiler Minimum (BOIL MIN)
The minimum boiler setting (
BOIL MIN) is the 
lowest water temperature that the control is allowed 
to use as a target temperature. During mild conditions, 
if the control calculates a target temperature that is 
below this setting, the target temperature is adjusted to 
at least the minimum setting. During this condition, if 
the unit is operating, the MIN segment turns on in the 
LCD while the target temperature or operating sensor 
temperature is viewed. For Copper Brute II units, this 
must be set no lower than 120°F (49°C) to protect the 
unit 
from condensing on the heat exchanger (see 
Figure 29
).
6.4.4  Boiler Maximum (BOIL MAX)
The boiler maximum (BOIL MAX) is the highest 
water temperature that the control is allowed to use 
as a target temperature. If the control does target 
BOIL MAX, and the boiler outlet sensor is near the 
BOIL MAX temperature, the MAX segment turns on 
in the LCD while the target, inlet, outlet or supply 
temperature is viewed (see 
Figure 29
).
6.4.5  Boiler Target Temperature
The target temperature is determined from 
the mode of operation. The control displays the 
temperature that is currently trying to maintain at the 
operating sensor as 
BOIL TARGET in the View menu. 
The operating sensor for modes 1, 3 and 4 is the outlet 
sensor (on the Copper Brute II). The operating sensor 
for modes 2 and 5 is the supply sensor (in the system 
or primary loop). If the control does not presently have 
a requirement for heat, it displays “- - -” in the LCD. 
There is no target temperature generated in mode 6 
(external controller mode).
6.4.6  Pump Operation
The pump terminals (Pmp Pmp) are energized 
with 24 VAC to control a field supplied pump 
contactor. During setpoint operation (modes 1 and 2), 
the terminals are energized whenever there is a heat 
demand. During dedicated DHW operation (mode 
3), the terminals are energized whenever there is an 
internal heat demand. During outdoor reset (modes 4 
and 5), the terminals are energized whenever there is 
either a heat demand and the control is not in Warm 
Weather Shut Down (WWSD), or whenever there is 
a setpoint demand. During WWSD, if the pump has 
not operated at least once every 70 hours, the control 
energizes the terminals for 10 seconds. This minimizes 
the possibility of the pump seizing during a long 
period of inactivity. During External Boiler Operation 
(mode 6), the pump contact closes whenever there is a 
heat demand.
Boiler Purge (
PUMP DLY– After a demand 
is satisfied, the control continues to operate the pump 
for a period of time. The length of time that the 
pump continues to run is based on the pump delay 
setting. Once the last stage of the control turns off, 
the control keeps the pump contacts energized for