Bradford-White Corp Copper Brute II Hydronic Boiler Manual De Usuario

Descargar
Página de 64
Page 44
 
B
RADFORD
 W
HITE
 C
ORP.
Figure 30. Temperature Control Outdoor Start Graph.
the time selected (between 0 and 10 minutes). When 
OFF
 is selected, there is no purging. When 
ON
 is 
selected, pump operation is continuous. Also, during 
outdoor reset, with the pump delay set to 
ON
, the pump 
continues to run even during Warm Weather Shut 
Down.
6.4.7  Setpoint Operation
When either mode 1 or 2 is selected, the control 
controls the water temperature based on a fixed 
setpoint. The setpoint temperature is set using the 
BOIL TARGET item in the ADJUST menu.
Heat Demand 
– For “heat demand” to exist, 
there must be continuity between the Com D (common 
demand) and the Ht D (heat demand) terminals. The 
Copper Brute II ships with a jumper between these 
terminals.
The control also evaluates the sensor(s) installed 
in the system, including the outlet sensor provided on 
the boiler when using mode 1. When the control senses 
continuity between Com D and Ht D terminals, and 
that the sensor reading is below the target temperature, 
the control will activate the Dem segment in the 
display.
The control energizes the pump (on pump 
mounted boilers) and energizes the Pmp Pmp 
terminals. The boiler pump segment is turned on in 
the display. The control then operates the stages to 
maintain the setpoint temperature.
6.4.8  Dedicated Domestic Hot Water
When mode 3 is selected, the control provides 
dedicated domestic hot water operation. 
Internal DHW Demand 
– A sensor is required 
to be connected on the SC2 and Sup/S terminals. 
An internal demand for DHW is generated when the 
temperature demand for DHW sensor drops ½ of the 
tank differential setting below the desired DHW tank 
temperature. The TANK TARGET setting is used to 
set the desired DHW tank temperature.
Once an internal demand is generated, the 
Dem segment turns on in the LCD. The control then 
closes the Pmp Pmp contact, which starts the pump 
and the control turns on the boiler pump segment in 
the display. The control then operates the stages to 
maintain the programmed boiler target temperature at 
the boiler outlet sensor. 
The boiler target temperature is set using the 
BOIL TARGET item in the Adjust menu. NOTE: 
External demand is not required in this mode of 
operation.
Tank Differential 
– A differential setting that 
operates ½ above and below the 
TANK TARGET is 
selectable using the 
TANK DIFF item in the Adjust 
menu.
6.4.9  Outdoor Reset Operation
When either mode 4 or 5 is selected, the control 
uses outdoor reset to control the water temperature. 
Outdoor reset adjusts the target temperature based 
on the outdoor air temperature and reset ratio. The 
reset ratio is determined from the Boiler Start, Boiler 
Design, Outdoor Start and Outdoor Design settings.
Heat Demand 
– For “heat demand” to exist, 
there must be continuity between the Com D (common 
demand) and the Ht D (heat demand) terminals. The 
Copper Brute II ships with a jumper between these 
terminals. 
The control also evaluates the sensor(s) installed 
in the system. If the control is not in warm weather 
shutdown (WWSD), and the sensor(s) are below the 
target temperature, the Dem segment is turned on 
in the display. The control energizes the pump (on 
pump mounted boilers) and energizes the Pmp-Pmp 
terminals, and the boiler pump segment is turned on 
in the display. The control then operates the stages to 
maintain the setpoint temperature.
Boiler Start (
BOIL START– The BOIL 
START temperature is the theoretical boiler supply 
water temperature that the heating system requires 
when the outdoor air temperature equals the OUTDR 
START temperature setting. The BOIL START is 
typically set to the desired building temperature (see 
Figure 30). 
Outdoor Start (
OUTDR START– The 
OUTDR START temperature is the outdoor air 
temperature at which the control provides the BOIL 
START water temperature to the system. The OUTDR 
START is typically set to the desired building 
temperature.
Outdoor Design (
OUTDR DSGN– The 
OUTDR DSGN is the outdoor air temperature that is