Ei Electronics Ei161RC Prospecto
Shannon Free Zone, Shannon, Co. Clare, Ireland.
Ph.
+353 61 471277
Fx.
+353 61 471053
Email.
eielectronics@eiltd.ie
Web:
www.eielectronics.com
E & OE As our policy is one of continuous product development, we reserve the right to alter product details without prior notice
.
Ei161RC DataSht RevB
Model
Ei161RC Ionisation
System Wiring
Wiring for Interconnected Alarms with optional Remote System Control Switch & Manual Call Point
Ensure correct wiring of the alarms and switches as mixing Live and Neutral will blow / damage interconnected units.
Technical Specification
Sensor
Ionisation
Sensitivity:
Complies with BS 5446 Part 1:
2000
2000
Source:
Americium 241 (33kBq)
Button Test:
Simulates the effect of smoke and
checks electronics and horn
checks electronics and horn
Automatic Self-Test:
Circuitry is tested every 40
seconds and unit beeps if fault is
detected
Supply Voltage:
230V AC, 50Hz
Battery back up:
Rechargeable Lithium cells
Power-On Indicator:
Continuous green LED
Alarm:
Electronic Piezoelectric horn
Alarm Sound Output:
85dB(A) (minimum) at 3m
Alarm Status:
Red LED flashes every second on
unit sensing fire
Normal Operating
Temperature Range:
Temperature Range:
0 to 40°C
Humidity Range:
15% to 95% Relative Humidity
Interconnect:
Up to 12 of these units can be
interconnected:
interconnected:
-
Ei161RC/164RC/166RC smoke or
heat alarms
- Ei261ENRC/261DENRC CO alarm
- Ei128RBU relay base
- Ei128RBU relay base
Use with optional control (see below)
Optional Controls:
-
Ei1529RC Control Switch
- MCP401RC Manual Call Point
Fixing:
Easi-fit mounting base
Plastic material:
UL94VO flame retardant
Dimensions:
145mm diameter x 40mm depth
Weight:
281g
Guarantee:
5 year (limited)
Approvals:
Kitemarked to BS EN 14604:2005
(License no. KM07862) and CE
certified
(License no. KM07862) and CE
certified
Specifications are subject to change