Ei Electronics Ei161RC 전단

다운로드
페이지 2
 
Shannon Free Zone, Shannon, Co. Clare, Ireland. 
Ph.
+353 61 471277   
Fx.
+353 61 471053   
 
Email.
 eielectronics@eiltd.ie
 
 
Web:
 www.eielectronics.com 
E & OE  As our policy is one of continuous product development, we reserve the right to alter product details without prior notice
.       
Ei161RC DataSht RevB
 
 
 
Model 
Ei161RC Ionisation 
System Wiring 
 
Wiring for Interconnected Alarms with optional Remote System Control Switch & Manual Call Point 
 
         
        
 
 
 
 
 
 
 
 
Ensure correct wiring of the alarms and switches as mixing Live and Neutral will blow / damage interconnected units. 
 
 
 
 
Technical Specification 
 
Sensor  
Ionisation 
 
Sensitivity:
 
Complies with BS 5446 Part 1: 
2000 
 
Source: 
Americium 241 (33kBq) 
 
Button Test:
 
Simulates the effect of smoke and 
checks electronics and horn 
 
Automatic Self-Test:
  Circuitry is tested every 40
 
seconds and unit beeps if fault is
 
detected 
 
Supply Voltage: 
230V AC, 50Hz 
 
Battery back up: 
Rechargeable Lithium cells 
 
Power-On Indicator:
   Continuous green LED 
 
Alarm:  
Electronic Piezoelectric horn 
 
Alarm Sound Output:
  85dB(A) (minimum) at 3m 
 
Alarm Status:
 
Red LED flashes every second on 
 
unit sensing fire
 
 
 
 
 
 
  
 
Normal Operating 
Temperature Range:
  0 to 40°C 
 
Humidity Range:
 
15% to 95% Relative Humidity 
 
Interconnect:
 
Up to 12 of these units can be 
interconnected: 
-
 Ei161RC/164RC/166RC smoke or 
   heat alarms 
 
- Ei261ENRC/261DENRC CO alarm 
- Ei128RBU relay base 
 
Use with optional control (see below) 
 
Optional Controls: 
Ei1529RC Control Switch
 
- MCP401RC Manual Call Point 
 
Fixing:
 
Easi-fit mounting base 
 
Plastic material:
 
UL94VO flame retardant 
 
Dimensions: 
145mm diameter x 40mm depth
 
 
Weight: 
281g
 
 
Guarantee:
 
5 year (limited) 
 
Approvals:
 
Kitemarked to BS EN 14604:2005 
(License no. KM07862) and CE 
certified
 
 
Specifications are subject to change