iLux™ Expansion Module 
 
Crestron CLS-EXP-DIMU 
Physical Description 
This section provides information on the connections, 
controls and indicators available on the CLS-EXP-DIMU. 
CLS-EXP-DIMU Overall Dimensions 
8.82 in
(22.40 cm)
6.39 in
(16.23 cm)
5.79 in
(14.71 cm)
4.99 in
(12.67 cm)
Ø 0.19 in
(Ø 0.48 cm)
8.31 in
(21.11 cm)
7.31 in
(18.57 cm)
Ø 0.25 in
(Ø 0.64 cm)
0.50 in
(1.27 cm)
3.18 in
(8.08 cm)
3.07 in
(7.80 cm)
1.64 in
(4.17 cm)
1.64 in
(4.17 cm)
2.02 in
(5.21 cm)
1.56 in
(3.96 cm)
 
CLS-EXP-DIMU (cover removed) 
PH
ASE
ST
A
T
U
S
PO
W
E
R
S1
ON
12
2
1
ON
S2
1
7
12
8
9
2
3
10
11
4
5
6
 
Connectors, Controls & Indicators 
# CONNECTORS, 
CONTROLS & 
INDICATORS 
DESCRIPTION 
1 FLUORESCENT 
OFF THRESHOLD 
(1) Recessed screwdriver-
adjustable trim pot, adjusts 
minimum brightness level. 
Covered by removable cap. 
PHASE LED 
(1) Yellow LED behind front 
panel; illuminates when 
operating in Reverse Phase 
mode. 
STATUS LED 
(1) Red LED behind front 
panel; illuminates when load 
output is on. 
POWER LED 
(1) Green LED behind front 
panel; indicates power is 
applied to the HOT terminal. 
5 S2 
2
1
ON
 
(1) Two-position DIP switch 
behind front panel; used to 
select the zero cross detection 
filter. 
For more information, refer to 
“Zero Cross Detection Filter” on 
page 6.  
S1 
ON
12
 
(1) Two-position DIP switch 
behind front panel; used to 
select dimming mode. 
For more information, refer to 
“Dimming Mode” on page 6. 
CTRL 
(1) Captive screw terminal, for 
control input from CLS-Series, 
CLW-Series* dimmers,  
CLX-DIM (all versions), or other 
Crestron incandescent 
dimmers. 
NEUT (INPUT) 
(1) Captive screw terminal, for 
neutral connection for control 
input. 
DIM OUT 
(1) Captive screw terminal for 
dimmed output to the load. 
10 
HOT 
(1) Captive screw terminal, for 
line power input. 
11 
NEUT (OUTPUT) 
(1) Captive screw terminal, 
neutral connection for line 
power input and load. 
12 
GROUND 
(1) Chassis ground bus bar. 
* CLW-Series 
device 
must 
have a dedicated neutral. 
4  
  Terminal Block & Module:  CLTI- & CLXI-2DIM8 
Installation Guide – DOC. 6682B