Reference lists define up to three timing references for the node and up to six BITS Out references. BITS Out
references define the timing references used by equipment that can be attached to the node's BITS Out pins on
the backplane. If you attach equipment to BITS Out pins, you normally attach it to a node with Line mode because
equipment near the external timing reference can be directly wired to the reference.
Note
• NE Reference
• BITS 1 Out
• BITS 2 Out
Step 5
In node view (single-shelf mode) or shelf view (multishelf mode), click the Provisioning > Timing > BITS Facilities
tabs.
Step 6
In the BITS In section, you can change the following information:
The BITS Facilities section sets the parameters for your BITS1 and BITS2 timing references. Many of these
settings are determined by the timing source manufacturer. If equipment is timed through BITS Out, you can set
timing parameters to meet the requirements of the equipment.
Note
• BITS In State
• Coding
• State
• Framing
• Sync Messaging
• Admin SSM
Step 7
In the BITS Out section, you can change the following information:
• Coding
• Framing
• AIS Threshold
• LBO
Step 8
Click Apply. Confirm that the changes appear.
Internal timing is Stratum 3 and is not intended for permanent use. All ONS 15454s should be timed to a
Stratum 2 or better primary reference source.
Caution
Step 9
Complete the "NTP-G103 Back Up the Database" procedure in the chapter, "Maintaining the Node" of the Cisco ONS
15454 DWDM Network Configuration Guide 
.
Stop. You have completed this procedure.
NTP-G112 Change the Node Timing Reference
This procedure enables automatic timing reference switching
or returns the node timing to normal operation.
Purpose
12