Samsung AS24UUQ Manual De Usuario

Descargar
Página de 40
30
If you need a pipe longer than 5 meters:
•  You must extend the assembly cable. 
•  You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.
Cutting or extending the pipe
A 5-meter pipe is supplied with the air conditioner (optional).
The length of the pipe can be:
Extended up to  : See table page 24
Shorten  up to : See table page 24
Make sure that you have the required tools (pipe cutter, reamer,  aring tool
and pipe holder).
If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut
edge remains at 90° with the side of the pipe (see examples of correctly and
incorrectly cut edges below).
Oblique
Rough
Burr
To prevent a gas leak, remove all burrs at the cut edge of the pipe using a
reamer.
Put a  are nut slightly into the pipe and modify the  are.
Check if you  ared the pipe correctly (see examples of incorrectly  ared pipes
below).
Uneven
Thickness
Cracked
Damaged
Surface
Inclined
Align the pipes to connect them easily. Tighten the  are nuts  rst with your
hands, and then with a torque wrench, applying the following torque:
For further details on how to connect to the outdoor unit and purge the air,
refer to page 35.
Pipe cutter
Pipe
Indoor outlet pipe
Connecting pipe
Flare nut
 
 
 Tighten the 
 nut with torque wrench according to 
 method. 
•   Excessive torque can be cause of gas leakage. 
90°± 2°
45°± 2°
R 0.4~0.8
B
Flare
Pipe
Outer Diameter (D)
Depth (A)
Flaring Size (B)
ø6.35 mm
1.3 mm
8.7 - 9.1 mm
12.8 - 13.2 mm
16.2 - 16.6 mm
19.3 - 19.7 mm
ø9.52 mm
1.8 mm
ø12.70 mm
2.0 mm
ø15.88 mm
2.2 mm
Outer
 
Diameter
Torque (kgf•cm)
N•m
(kgf•cm)
ø6.35  mm
14 ~ 18
140 ~ 180
ø9.52  mm
34 ~ 42
350 ~ 430
ø12.70 mm
49 ~ 61
500 ~ 620
ø15.88 mm
68 ~ 82
690 ~ 830