Setup 29 
Rack planning resources 
The rack resource kit ships with all HP branded or Compaq branded 9000, 10000, and H9 series racks. 
For more information on the content of each resource, refer to the rack resource kit documentation. 
If you intend to deploy and configure multiple servers in a single rack, refer to the white paper on high-
 
Optimum environment 
When installing the server in a rack, select a location that meets the environmental standards described in 
this section. 
 
Space and airflow requirements 
To allow for servicing and adequate airflow, observe the following space and airflow requirements when 
deciding where to install a rack: 
 
Leave a minimum clearance of 63.5 cm (25 in) in front of the rack. 
 
Leave a minimum clearance of 76.2 cm (30 in) behind the rack. 
 
Leave a minimum clearance of 121.9 cm (48 in) from the back of the rack to the back of another 
rack or row of racks. 
HP servers draw in cool air through the front door and expel warm air through the rear door. Therefore, 
the front and rear rack doors must be adequately ventilated to allow ambient room air to enter the 
cabinet, and the rear door must be adequately ventilated to allow the warm air to escape from the 
cabinet. 
  
 
CAUTION:
  To prevent improper cooling and damage to the equipment, do not block the 
ventilation openings. 
  
When vertical space in the rack is not filled by a server or rack component, the gaps between the 
components cause changes in airflow through the rack and across the servers. Cover all gaps with 
blanking panels to maintain proper airflow. 
  
 
CAUTION:
  Always use blanking panels to fill empty vertical spaces in the rack. This 
arrangement ensures proper airflow. Using a rack without blanking panels results in improper 
cooling that can lead to thermal damage. 
  
The 9000 and 10000 Series Racks provide proper server cooling from flow-through perforations in the 
front and rear doors that provide 64 percent open area for ventilation.  
  
 
CAUTION:
  When using a Compaq branded 7000 Series rack, you must install the high 
airflow rack door insert [P/N 327281-B21 (42U) or P/N 157847-B21 (22U)] to provide 
proper front-to-back airflow and cooling.