HP proliant dl380 Manual De Usuario

Descargar
Página de 113
 
Setup 31 
Electrical grounding requirements 
The server must be grounded properly for proper operation and safety. In the United States, you must 
install the equipment in accordance with NFPA 70, 1999 Edition (National Electric Code), Article 250, 
as well as any local and regional building codes. In Canada, you must install the equipment in 
accordance with Canadian Standards Association, CSA C22.1, Canadian Electrical Code. In all other 
countries, you must install the equipment in accordance with any regional or national electrical wiring 
codes, such as the International Electrotechnical Commission (IEC) Code 364, parts 1 through 7. 
Furthermore, you must be sure that all power distribution devices used in the installation, such as branch 
wiring and receptacles, are listed or certified grounding-type devices. 
Because of the high ground-leakage currents associated with multiple servers connected to the same 
power source, HP recommends the use of a PDU that is either permanently wired to the building’s branch 
circuit or includes a nondetachable cord that is wired to an industrial-style plug. NEMA locking-style plugs 
or those complying with IEC 60309 are considered suitable for this purpose. Using common power outlet 
strips for the server is not recommended. 
 
Rack warnings 
  
 
WARNING:
  To reduce the risk of personal injury or damage to the equipment, be sure that: 
 
The leveling jacks are extended to the floor. 
 
The full weight of the rack rests on the leveling jacks. 
 
The stabilizing feet are attached to the rack if it is a single-rack installation.  
 
The racks are coupled together in multiple-rack installations.  
 
Only one component is extended at a time. A rack may become unstable if more than one 
component is extended for any reason.  
  
 
  
 
WARNING:
  To reduce the risk of personal injury or equipment damage when unloading a 
rack: 
 
At least two people are needed to safely unload the rack from the pallet. An empty 42U 
rack can weigh as much as 115 kg (253 lb), can stand more than 2.1 m (7 ft) tall, and 
may become unstable when being moved on its casters. 
 
Never stand in front of the rack when it is rolling down the ramp from the pallet. Always 
handle the rack from both sides. 
  
 
Identifying the contents of the server shipping carton 
Unpack the server shipping carton and locate the materials and documentation necessary for installing the 
server. All the rack mounting hardware necessary for installing the server into the rack is included with the 
rack or the server. 
The contents of the server shipping carton include: 
 
Server 
 
Power cord 
 
Hardware documentation, Documentation CD, and software products 
 
Rack-mounting hardware 
In addition to the supplied items, you may need: