Toshiba 4200FA Manual De Usuario

Descargar
Página de 66
TOSHIBA 
 
6.0 Operating the UPS 
6.1 
Operating the UPS 
 
6.1.1 
AC Input Mode (normal operation) 
The following illustration shows circuit power flow when the UPS is operating normally in the 
AC input mode. The converter of the UPS, including a boost chopper circuit, converts the AC 
input power to DC power. The boost chopper circuit maintains a constant voltage and provides 
current limiting for battery charging. It also supplies a DC voltage of the proper level to the 
inverter section. The inverter section generates a high quality sine wave output voltage. The 
UPS batteries always maintain a charge during normal UPS operation. 
 
Converter
 
Inverter
 
Static 
Bypass
 
Charger/ 
Chopper
 
Isolating 
XFMR
 
Input 
Power 
MCCB
 
Power Flow
 
 
 
 
Output 
Power 
 
 
 
 
 
 
 
 
External 
Batteries
 
 
 
 
Power flow in AC input mode for the 4200FA 80 kVA UPS 
 
6.1.2 Bypass 
Mode 
If the UPS detects an overload or develops an internal fault, power flow is automatically 
switched from the main circuit of the UPS to the Bypass circuit.  Power flow through the 
Bypass is shown in the following illustration. This changeover occurs automatically in less than 
4 milliseconds. The switching period is not long enough to cause interruptions to occur in most 
loads.  If the power flow is transferred to the bypass circuit because of an overload and the 
overload condition ends within a specified period of time, normal operation will resume 
automatically (see Section 6.16 Overload Operation). 
If the power flow is transferred to the bypass circuit due to a fault condition, the power flow 
must be transferred manually from the Bypass circuit back to the inverter circuit after the fault 
is cleared (see Section 6.11 Start-up Procedure). 
 
Converter
 
Inverter
 
Static 
Bypass
 
Charger/ 
Chopper
 
Isolating 
XFMR
 
External 
Input 
Power 
MCCB
 
Power Flow
 
Batteries
 
 
 
 
Output 
Power 
 
 
 
 
 
 
 
 
 
 
 
Power flow in circuit-bypass mode for the 4200FA 80 kVA UPS 
4200 FA User’s Manual   
29