6.1.3 
Battery Backup Mode 
The following illustration shows power flow during the battery backup mode. In the event of an 
AC power failure the batteries of the UPS instantly begin supplying DC power to the UPS to the 
main inverter circuit. This circuit converts the DC power into AC power. The AC power is 
available at the output of the unit. This back-up process will continue until the UPS battery 
voltage drops below a specific minimum level. At which time the batteries cease supplying 
power to the load. 
This minimum level is the shutdown voltage minimum (V min). The rated battery voltage table 
on page 36 shows (V min). The battery backup time and discharge process is explained in 
Section 6.2. 
 
Static 
 
Bypass
 
 
MCCB
 
 
 
 
 
 
 
 
 
 
 
 
 
Power flow in battery backup mode for the 4200FA 80 kVA UPS 
 
 
6.1.4 
External Maintenance Bypass (Customer Supplied) 
An external maintenance bypass may be installed in parallel with the UPS to allow servicing of 
the UPS while maintaining power to the load.  Contact an authorized service representative for 
further information. 
 
CAUTION 
Ensure the UPS is set to BYPASS mode before switching the 
external bypass from UPS to MAINTENANCE BYPASS.
 
 
High transient currents may result if the external bypass is engaged 
while the UPS is in normal mode. 
 
Converter
 
Inverter
 
Charger/ 
Chopper
 
Isolating 
XFMR
 
External 
Batteries
 
Output 
Power 
Input 
Power 