Toshiba 4200FA Manual De Usuario
![Toshiba](https://files.manualsbrain.com/attachments/acaaaa9cc6b763ccfc72ced2ae95d9c94b8b8632/common/fit/150/50/8adbcbcd45c75dc53932fc9caf6f2740daed52d836b76efbd0162ac2599f/brand_logo.png)
TOSHIBA
28
4.5 Communication
Interface
4.5.1 Remote Contact
This interface is a standard feature and is available as dry switch contacts through a DB9 male
connector located on the front of the UPS. The following schematic shows the contact state
and pin assignment for each signal and the associated DB9 connector pin-out.
connector located on the front of the UPS. The following schematic shows the contact state
and pin assignment for each signal and the associated DB9 connector pin-out.
Notes:
1) Pin “switches” are shown in their inactive states. Example: (if battery voltage is low, pin 7 will be
connected to System Common).
2) Contacts are rated at 30 VDC, 0.1 amps; 125 VAC, 3 amps.
3) Pin number “3” is not used.
5 System Common
6 Bypass Active
Fault Signal Detect
1
2
8 UPS On-line
7 Battery Voltage Low
Battery Discharge
9
4
DB9 Male Connector Outline
(Facing Connector)
1 2 3 4 5
6 7 8 9