Toshiba 4200FA Manual De Usuario

Descargar
Página de 66
TOSHIBA 
 
43 
5.15 
LCD (Liquid Crystal Display) Functions 
The LCD screen is a 4-line by 20-character wide display. The LCD display contains information 
about the operation of the UPS. It should be used in conjunction with the LED display and the 
audible alarms for total system monitoring. The LCD displays certain information only on 
specific lines of the display. The UPS operating mode and conditions determines the 
information shown.  These messages are shown in the following line message charts.  
 
 
5.15.1  Line-1 System Messages 
Line-1 messages are based on the operating mode. The following chart shows all 
allowable Line-1 messages, which occur while starting up and while in main monitor 
(MONI) screen mode. 
 
LINE-1 MESSAGES 
Display Message 
Translation 
- UPS START UP - 
Displayed when UPS is in the start-up condition 
or display board is resetting. 
- BYPASS OPERATION - 
Displayed when the UPS is in Bypass 
Operation. 
- UPS ON-LINE - 
Displayed when the inverter is running, and no 
Utility abnormality exists. 
- BATTERY DISCHARGE - 
Displayed during abnormal Utility occurrences; 
inverter is supplying power from batteries. (UPS 
shuts down after V (min.) is reached. 
- OUTPUT SHUTDOWN - 
Displayed during power failure if V (min.) is 
reached, an EPO is received, or after 
completion of Start-Up Sequence of the Inverter 
and Bypass is not available. 
- BATTERY BACKUP - 
Displayed during input power failure. 
 
 
5.15.2  Line-2 System Fault Messages 
Line-2 fault messages are automatically displayed when a system fault is detected. 
 
LINE-2 MESSAGES 
Display Message 
Translation 
DCOC DC 
Over-current 
DCUB DC 
Unbalanced 
DCOV DC 
Over-voltage 
OH Overheat 
(internal) 
OL Output 
Overload 
VOUV Inverter 
Under-voltage 
VOOV Inverter 
Over-voltage 
 
 
5.15.3  Line-3 System Messages 
Line–3 messages show load current information, and user selected instructions.